Multiple outdoor unit installation
• When the upper space is open:
Unit: in (mm)
When there are obstacles at the rear only. When there are obstacles at the front only.
12 (300)
or more
10 (250)
or more
60 (1,500)
or more
10 (250) or more
When there are obstacles at the front and
rear.
20 (500)
or more
60 (1,500)
or more
10 (250)
or mor
e
• When there is an obstruction in the upper space:
Unit: in (mm)
When there are obstacles at the rear and above.
60 (1,500) or more
20 (500) or more
10 (250)
or more
10 (250)
or more
Max. 11
(300)
60 (1,500)
or more
- 71 -
3-1. Models: RP1724HJVXA and RP1730HJVXA 3. Installation space
OUTDOOR UNIT
RP1724-1748HJVXA
OUTDOOR UNIT
RP1724-1748HJVXA