7. HIGH TEMPERATURE RELEASE CONTROL (Heating mode)
In heating mode, compressor frequency is controlled as following
based on the detection value of the indoor evaporator coil temperature sensor.
RP1724HJVXA
RP1730HJVXA
Indoor evaporator coil
temperature
It returns to the normal operation
145.4°F
(63°C)
compressor stop
131°F
(55°C)
127.4°F
(53°C)
The compressor frequency is
decreased 15rps every 120 seconds.
The compressor frequency is
decreased 2rps every 120 seconds.
The compressor frequency is
Maintenance of status quo.
122°F
(50°C)
04-36