04-37
RP1736HJVXA
RP1748HJVXA
Discharge pressure rises
Release
The compressor frequency is
decreased 2rps every 120 seconds.
The compressor frequency is
decreased 15rps every 120 seconds.
A psi (A MPa)
B psi (B MPa)
C psi (C MPa)
Release
Stable range
Condenser coil
temperature
5°F(-15°C)
<
=
Tn<8.6°F(-13°C)
-13°F(-25°C)
<
=
Tn<5°F(-15°C)
-20.2°F(-29°C)
<
=
Tn<-13°F(-25°C)
Tn<-20.2°F(-29°C)
8.6°F(-13°C)
<
=
Tn<12.2°F(-11°C)
478.62 psl
(3.30 MPa)
464.12 psl
(3.20 MPa)
435.11 psl
(3.00 MPa)
377.10 psl
(2.60 MPa)
333.59 psl
(2.30 MPa)
449.62 psl
(3.10 MPa)
478.62 psl
(3.00 MPa)
406.11 psl
(2.80 MPa)
362.59 psl
(2.50 MPa)
319.08 psl
(2.20 MPa)
406.11 psl
(2.80 MPa)
391.60 psl
(2.70 MPa)
377.10 psl
(2.60 MPa)
333.59 psl
(2.30 MPa)
290.08 psl
(2.00 MPa)
Discharge pressure [psi(MPa)]
A B C