17
GENERAL DATA - RQRM
NOMINAL SIZES 2.5-4 TONS [8.7-13.6 kW]
Model RQRM- Series A048JK A060JK
Cooling Performance
1
Gross Cooling Capacity Btu [kW] 46,500 [13.62] 57,500 [16.85]
EER, SEER
2
13/16 12/15
Nominal CFM/AHRI Rated CFM [L/s] 1600/1525 [755/720] 2000/1900 [944/897]
AHRI Net Cooling Capacity Btu [kW] 45,500 [13.33] 56,000 [16.41]
Net Sensible Capacity Btu [kW] 34,700 [10.17] 41,450 [12.14]
Net Latent Capacity Btu [kW] 10,800 [3.16] 14,550 [4.26]
Net System Power kW 3.45 4.63
Heating Performance [Heat Pumps]
High Temp. Btuh [kW] Rating 43,500 [12.75] 54,800 [16.06]
System Power KW / COP 3.19/4 4.2/3.82
Low Temp. Btuh [kW] Rating 23,800 [6.97] 31,600 [9.26]
System Power KW / COP 2.79/2.5 3.65/2.54
HSPF (Btu/Watts-hr) 8.5 8.5
Compressor
No/Type 1/Scroll1/Scroll 1/Scroll
Outdoor Sound Rating (dB)
5
78 78
Outdoor Coil - Fin Type Louvered Louvered
Tube Type Rifled Rifled
Tube Size in. [mm] OD 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 16.54 [1.54] 16.54 [1.54]
Rows / FPI [FPcm] 2 / 18 [7] 2 / 18 [7]
Refrigerant Control TX Valves TX Valves
Indoor Coil - Fin Type Louvered Louvered
Tube Type Rifled Rifled
Tube Size in. [mm] 0.375 [9.5] 0.375 [9.5]
Face Area sq. ft. [sq. m] 5.78 [0.54] 5.78 [0.54]
Rows / FPI [FPcm] 4 / 13 [5] 4 / 13 [5]
Refrigerant Control TX Valves TX Valves
Drain Connection No./Size in. [mm] 1/1 [25.4] 1/1 [25.4]
Outdoor Fan - Type Propeller Propeller
No. Used/Diameter in. [mm] 1/24 [609.6] 1/24 [609.6]
Drive Type/No. Speeds Direct/1 Direct/1
CFM [L/s] 4200 [1982] 4200 [1982]
No. Motors/HP 1 at 1/3 HP 1 at 1/3 HP
Motor RPM 1075 1075
Indoor Fan - Type FC Centrifugal FC Centrifugal
No. Used/Diameter in. [mm] 1/11x9 [279x229] 1/11x9 [279x229]
Drive Type/No. Speeds Direct/2 Direct/2
No. Motors 11
Motor HP 3/4 1
Motor RPM 1050 1050
Motor Frame Size 48 48
Filter - Type Field Supplied Field Supplied
Furnished No No
(NO.) Size Recommended in. [mm x mm x mm] (1)1x24x24 [25x610x610] (1)1x24x24 [25x610x610]
Refrigerant Charge Oz. [g] 216 [6124] 202 [5727]
Weights
Net Weight lbs. [kg] 481 [218] 482 [219]
Ship Weight lbs. [kg] 507 [230] 508 [230]
NOTES:
1. Cooling Performance is rated at 95° F ambient, 80° F entering dry bulb, 67° F entering wet bulb. Gross capacity does not include the effect of fan motor heat. AHRI capaci-
ty is net and includes the effect of fan motor heat. Units are suitable for operation in CFM range shown in airflow tables. Units are certified in accordance with the Unitary
Air Conditioner Equipment certification program, which is based on AHRI Standard 210/240 or 360.
2. EER and/or SEER are rated at AHRI conditions and in accordance with DOE test procedures.
3. Heating Performance is rated at 47° F ambient, 70° F entering dry bulb for High Temp rating and 17° F ambient, 70° F entering dry bulb for Low Temp rating. Performance
ratings do include the effect of fan motor heat.
4. Outdoor Sound Rating shown is tested in accordance with AHRI Standard 270.