EasyManua.ls Logo

Rheem RRKA-A036CK04E - SYSTEMS PERFORMANCE-RRKA-SERIES

Rheem RRKA-A036CK04E
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
SYSTEMS PERFORMANCE—RRKA- SERIES
GROSS SYSTEMS PERFORMANCE DATA—RRKA-A036
ENTERING INDOOR AIR @ 80°F [26.7°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481] 1320 [623] 1200 [566] 1020 [481]
DR
.27 .26 .24 .27 .26 .24 .27 .26 .24
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.9 [12.57]
23.4 [6.86]
2.9
42.2 [12.37]
22.2 [6.51]
2.9
41.2 [12.07]
20.4 [5.98]
2.8
41.4 [12.13]
28.2 [8.26]
3.0
40.7 [11.93]
27.0 [7.91]
2.9
39.7 [11.63]
25.2 [7.39]
2.9
39.7 [11.63]
32.8 [9.61]
2.9
39.0 [11.43]
31.6 [9.26]
2.9
38.0 [11.14]
29.7 [8.70]
2.8
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.8 [12.25]
23.3 [6.83]
3.1
41.1 [12.05]
22.1 [6.48]
3.1
40.1 [11.75]
20.3 [5.95]
3.0
40.3 [11.81]
28.1 [8.24]
3.2
39.7 [11.63]
26.9 [7.88]
3.1
38.6 [11.31]
25.1 [7.36]
3.1
38.6 [11.31]
32.7 [9.58]
3.1
37.9 [11.11]
31.5 [9.23]
3.0
36.9 [10.81]
29.7 [8.70]
3.0
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.0 [12.02]
23.1 [6.77]
3.3
40.3 [11.81]
21.9 [6.42]
3.3
39.3 [11.52]
20.1 [5.89]
3.2
39.5 [11.58]
27.9 [8.18]
3.3
38.8 [11.37]
26.7 [7.82]
3.3
37.8 [11.08]
24.9 [7.30]
3.3
37.8 [11.08]
32.5 [9.52]
3.3
37.1 [10.87]
31.3 [9.17]
3.2
36.1 [10.58]
29.5 [8.65]
3.2
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
40.2 [11.78]
22.9 [6.71]
3.5
39.5 [11.58]
21.6 [6.33]
3.5
38.5 [11.28]
19.8 [5.80]
3.4
38.8 [11.37]
27.7 [8.12]
3.5
38.1 [11.17]
26.4 [7.74]
3.5
37.1 [10.87]
24.6 [7.21]
3.5
37.0 [10.84]
32.2 [9.44]
3.4
36.4 [10.67]
31.0 [9.09]
3.4
35.3 [10.35]
29.2 [8.56]
3.4
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.5 [11.58]
22.5 [6.59]
3.7
38.8 [11.37]
21.3 [6.24]
3.6
37.8 [11.08]
19.4 [5.69]
3.6
38.0 [11.14]
27.3 [8.00]
3.7
37.3 [10.93]
26.1 [7.65]
3.7
36.3 [10.64]
24.2 [7.09]
3.6
36.3 [10.64]
31.9 [9.35]
3.6
35.6 [10.43]
30.6 [8.97]
3.6
34.6 [10.14]
28.8 [8.44]
3.6
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
38.7 [11.34]
22.0 [6.45]
3.9
38.0 [11.14]
20.8 [6.10]
3.8
37.0 [10.84]
19.0 [5.57]
3.8
37.2 [10.90]
26.8 [7.85]
3.9
36.5 [10.70]
25.6 [7.50]
3.9
35.5 [10.40]
23.8 [6.98]
3.8
35.5 [10.40]
31.4 [9.20]
3.8
34.8 [10.20]
30.2 [8.85]
3.8
33.8 [9.91]
28.4 [8.32]
3.7
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
37.7 [11.05]
21.5 [6.30]
4.0
37.0 [10.84]
20.2 [5.92]
4.0
36.0 [10.55]
18.4 [5.39]
4.0
36.2 [10.61]
26.3 [7.71]
4.1
35.5 [10.40]
25.0 [7.33]
4.1
34.5 [10.11]
23.2 [6.80]
4.0
34.5 [10.11]
30.8 [9.03]
4.0
33.8 [9.91]
29.6 [8.67]
4.0
32.8 [9.61]
27.8 [8.15]
3.9
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.4 [10.67]
20.8 [6.10]
4.2
35.7 [10.46]
19.6 [5.74]
4.2
34.7 [10.17]
17.8 [5.22]
4.2
34.9 [10.23]
25.6 [7.50]
4.3
34.2 [10.02]
24.4 [7.15]
4.2
33.2 [9.73]
22.6 [6.62]
4.2
33.2 [9.73]
30.2 [8.85]
4.2
32.5 [9.52]
29.0 [8.50]
4.2
31.5 [9.23]
27.2 [7.97]
4.1
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
34.7 [10.17]
20.1 [5.89]
4.4
34.0 [9.96]
18.9 [5.54]
4.4
33.0 [9.67]
17.1 [5.01]
4.3
33.3 [9.76]
24.9 [7.30]
4.5
32.6 [9.55]
23.7 [6.95]
4.4
31.6 [9.26]
21.9 [6.42]
4.4
31.5 [9.23]
29.5 [8.65]
4.4
30.9 [9.06]
28.3 [8.29]
4.3
29.8 [8.73]
26.4 [7.74]
4.3
GROSS SYSTEMS PERFORMANCE DATA—RRKA-A042
ENTERING INDOOR AIR @ 80°F [26.7°C]
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s] 1540 [727] 1400 [661] 1190 [562] 1540 [727] 1400 [661] 1190 [562] 1540 [727] 1400 [661] 1190 [562]
DR
.28 .27 .25 .28 .27 .25 .28 .27 .25
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
48.6 [14.24]
27.1 [7.94]
3.2
47.9 [14.04]
25.7 [7.53]
3.1
46.7 [13.69]
23.6 [6.92]
3.1
46.1 [13.51]
32.0 [9.38]
3.1
45.4 [13.31]
30.6 [8.97]
3.1
44.2 [12.95]
28.5 [8.35]
3.1
44.3 [12.98]
38.3 [11.22]
3.1
43.6 [12.78]
36.9 [10.81]
3.1
42.4 [12.43]
34.9 [10.23]
3.0
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
48.0 [14.07]
26.6 [7.80]
3.4
47.2 [13.83]
25.2 [7.39]
3.3
46.1 [13.51]
23.1 [6.77]
3.3
45.5 [13.33]
31.5 [9.23]
3.3
44.7 [13.10]
30.1 [8.82]
3.3
43.6 [12.78]
28.1 [8.24]
3.3
43.7 [12.81]
37.8 [11.08]
3.3
42.9 [12.57]
36.4 [10.67]
3.3
41.8 [12.25]
34.4 [10.08]
3.2
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
47.3 [13.86]
26.3 [7.71]
3.6
46.5 [13.63]
24.9 [7.30]
3.5
45.3 [13.28]
22.9 [6.71]
3.5
44.8 [13.13]
31.2 [9.14]
3.5
44.0 [12.90]
29.9 [8.76]
3.5
42.9 [12.57]
27.8 [8.15]
3.5
43.0 [12.60]
37.6 [11.02]
3.5
42.2 [12.37]
36.2 [10.61]
3.5
41.1 [12.05]
34.1 [9.99]
3.4
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.4 [13.60]
26.2 [7.68]
3.8
45.6 [13.36]
24.8 [7.27]
3.7
44.5 [13.04]
22.7 [6.65]
3.7
43.9 [12.87]
31.1 [9.11]
3.7
43.2 [12.66]
29.7 [8.70]
3.7
42.0 [12.31]
27.6 [8.09]
3.7
42.1 [12.34]
37.4 [10.96]
3.7
41.4 [12.13]
36.0 [10.55]
3.7
40.2 [11.78]
33.9 [9.94]
3.6
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.4 [13.31]
26.0 [7.62]
4.0
44.7 [13.10]
24.6 [7.21]
3.9
43.5 [12.75]
22.6 [6.62]
3.9
42.9 [12.57]
30.9 [9.06]
3.9
42.2 [12.37]
29.6 [8.67]
3.9
41.0 [12.02]
27.5 [8.06]
3.9
41.1 [12.05]
37.2 [10.90]
3.9
40.4 [11.84]
35.9 [10.52]
3.9
39.2 [11.49]
33.8 [9.91]
3.8
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
44.3 [12.98]
25.8 [7.56]
4.2
43.5 [12.75]
24.4 [7.15]
4.1
42.3 [12.40]
22.4 [6.56]
4.1
41.8 [12.25]
30.7 [9.00]
4.1
41.0 [12.02]
29.3 [8.59]
4.1
39.9 [11.69]
27.3 [8.00]
4.1
40.0 [11.72]
37.0 [10.84]
4.1
39.2 [11.49]
35.7 [10.46]
4.1
38.1 [11.17]
33.6 [9.85]
4.0
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.9 [12.57]
25.4 [7.44]
4.4
42.1 [12.34]
24.0 [7.03]
4.3
41.0 [12.02]
22.0 [6.45]
4.3
40.4 [11.84]
30.3 [8.88]
4.3
39.7 [11.63]
29.0 [8.50]
4.3
38.5 [11.28]
26.9 [7.88]
4.2
38.6 [11.31]
36.7 [10.76]
4.3
37.9 [11.11]
35.3 [10.35]
4.3
36.7 [10.76]
33.2 [9.73]
4.2
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
41.3 [12.10]
24.8 [7.27]
4.6
40.6 [11.90]
23.4 [6.86]
4.5
39.4 [11.55]
21.3 [6.24]
4.5
38.8 [11.37]
29.7 [8.70]
4.5
38.1 [11.17]
28.3 [8.29]
4.5
36.9 [10.81]
26.3 [7.71]
4.4
37.0 [10.84]
36.0 [10.55]
4.5
36.3 [10.64]
34.6 [10.14]
4.5
35.1 [10.29]
32.6 [9.55]
4.4
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.5 [11.58]
23.8 [6.98]
4.8
38.7 [11.34]
22.4 [6.56]
4.7
37.6 [11.02]
20.3 [5.95]
4.7
37.0 [10.84]
28.7 [8.41]
4.7
36.3 [10.64]
27.3 [8.00]
4.7
35.1 [10.29]
25.3 [7.41]
4.6
35.2 [10.32]
35.0 [10.26]
4.7
34.5 [10.11]
33.6 [9.85]
4.6
33.3 [9.76]
31.6 [9.26]
4.6
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions

Related product manuals