Rheem RRPL-B - Furnace Troubleshooting Guide

Rheem RRPL-B
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15 SECOND PREPURGE
IS NEGATIVE PRESSURE SYSTEM CLOSED?
(BOTH ON 2 STAGE HT)
THE SYSTEM WILL ATTEMPT TO LIGHT 3 TIMES (4 TIMES 2 STG HT) WITH A 60 SECOND
INTER-PURGE BETWEEN TRIES. IF AFTER THE THIRD TIME THE BURNERS
DO NOT LIGHT, THE SYSTEM WILL LOCK OUT. THE SYSTEM
WILL ATTEMPT TO LIGHT 3 TIMES (4 TIMES 2 STG HT ) EACH HOUR UNTIL THE BURNERS LIGHT
OR THE THERMOSTAT IS RESET.
FIGURE 63
105