XIII. MISCELLANEOUS
1 Horsepower per Compressor
2. Amp Draw Per Motor. Multiply Value by Number of Motors to Determine Total Amps.
-
B024JK04 -B024JK06 -B024JK08 -B030JK04 -B030JK06 -B030JK08 -B030JK10
U
nit Operating Voltage
R
ange
1
87-253 187-253 187-253 187-253 187-253 187-253 187-253
M
inimum Circuit
A
mmpacity
19/19 19/19 19/19 22/22 22/22 22/22 22/22
M
inimum Overcurrent
P
rotection Device Size
20/20 20/20 20/20 25/25 25/25 25/25 25/25
Maximum Overcurrent
Protection Device Size
3
0/30 30/30 30/30 35/35 35/35 35/35 35/35
N
o. 1111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1111111
H
P 2 1/6 2 1/6 2 1/6 2 2/3 2 2/3 2 2/3 2 2/3
R
PM 3450 3450 3450 3450 3450 3450 3450
Amps (RLA) 12.8/12.8 12.8/12.8 12.8/12.8 14.1/14.1 14.1/14.1 14.1/14.1 14.1/14.1
Amps (LRA) 58.3/58.3 58.3/58.3 58.3/58.3 73/73 73/73 73/73 73/73
No. 1111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1111111
HP 1/3 1/3 1/3 1/3 1/3 1/3 1/3
Amps (FLA) 1.3 1.3 1.3 1.3 1.3 1.3 1.3
Amps (LRA) 2.3 2.3 2.3 2.3 2.3 2.3 2.3
No. 1111111
Volts 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Phase 1111111
HP 1/4 1/4 1/4 1/2 1/2 1/2 1/2
Amps (FLA) 1.3 1.3 1.3 2.4 2.4 2.4 2.4
Amps (LRA) 2.3 2.3 2.3 5.1 5.1 5.1 5.1
Condenser MotorEvaporator Fan
E
LECTRICAL DATA - RRNL SERIES
Unit InformationCompressor Motor
-
B036CK04 -B036CK06
187-253 187-253
1
7/17 17/17
2
0/20 20/20
25/25 25/25
11
208/230 208/230
3
3
3
1/3 3 1/3
3450 3450
10.4/10.4 10.4/10.4
88/88 88/88
11
208/230 208/230
11
1/3 1/3
1.3 1.3
2.3 2.3
11
208/230 208/230
11
1/2 1/2
2.4 2.4
5.1 5.1