208-240 VOLT, SINGLE PHASE, 60 HZ, AUXILLARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION
Single Power Supply For Both Unit And Heater Kit Separate Power Supply For Both Unit And Heater Kit
Over Current
Protective Device Size
Min/Max @
208 V
Min/Max @
240 V
Min/Max @
208 V
Min/Max @
240 V
No Heat - - - - - 20/20 25/30 25/30 - - 20/20 25/30 25/30
05J 1 1 3.6/4.8 12.28/16.38 17.33/20 24/27 25/30 30/30 22/25 25/25 - - -
07J 1 1 5.4/7.2 18.42/24.56 26/30 35/40 35/35 40/40 33/38 35/40 - - -
10J 2 1 7.2/9.6 24.57/32.76 34.7/40 46/52 50/50 60/60 44/50 45/50 - - -
No Heat - - - - - 21/21 25/35 25/35 - - 21/21 25/35 25/35
05J 1 1 3.6/4.8 12.28/16.38 17.33/20 24/28 25/35 30/35 22/25 25/25 - - -
07J 1 1 5.4/7.2 18.42/24.56 26/30 35/40 35/35 40/40 33/38 35/40 - - -
10J 2 1 7.2/9.6 24.57/32.76 34.7/40 46/53 50/50 60/60 44/50 45/50 - - -
15J 3 2 10.8/14.4 36.85/49.13 52/60 68/78 70/70 80/80 65/75 70/80 - - -
No Heat - - - - - 26/26 30/40 30/40 - - 26/26 30/40 30/40
05J 1 1 3.6/4.8 12.28/16.38 17.33/20 26/29 30/40 30/40 22/25 25/25 - - -
07J 1 1 5.4/7.2 18.42/24.56 26/30 36/41 40/40 45/45 33/38 35/40 - - -
10J 2 1 7.2/9.6 24.57/32.76 34.7/40 47/54 50/50 60/60 44/50 45/50 - - -
15J 3 2 10.8/14.4 36.85/49.13 52/60 69/79 70/70 80/80 65/75 70/80 - - -
No Heat - - - - - 27/27 35/40 35/40 - - 27/27 35/40 35/40
05J 1 1 3.6/4.8 12.28/16.38 17.33/20 27/29 35/40 35/40 22/25 25/25 - - -
07J 1 1 5.4/7.2 18.42/24.56 26/30 36/41 40/40 45/45 33/38 35/40 - - -
10J 2 1 7.2/9.6 24.57/32.76 34.7/40 47/54 50/50 60/60 44/50 45/50 - - -
15J 3 2 10.8/14.4 36.85/49.13 52/60 69/79 70/70 80/80 65/75 70/80 - - -
20J 4 2 14.4/19.2 49.12/65.52 69.33/80 91/104 100/100 110/110 87/100 90/100 - - -
No Heat - - - - - 32/32 40/50 40/50 - - 32/32 40/50 40/50
05J 1 1 3.6/4.8 12.28/16.38 17.33/20 32/32 35/45 35/45 22/25 25/25 - - -
07J 1 1 5.4/7.2 18.42/24.56 26/30 37/42 40/45 45/45 33/38 35/40 - - -
10J 2 1 7.2/9.6 24.57/32.76 34.7/40 48/54 50/50 60/60 44/50 45/50 - - -
15J 3 2 10.8/14.4 36.85/49.13 52/60 69/79 70/70 80/80 65/75 70/80 - - -
20J 4 2 14.4/19.2 49.12/65.52 69.33/80 91/104 100/100 110/110 87/100 90/100 - - -
No Heat - - - - - 50/60 50/60 - - 0 50/60 50/60
05J 1 1 3.6/4.8 12.28/16.38 17.33/20 41/41 50/60 50/60 22/25 25/25 - - -
07J 1 1 5.4/7.2 18.42/24.56 26/30 41/45 50/60 50/60 33/38 35/40 - - -
10J 2 1 7.2/9.6 24.57/32.76 34.7/40 51/58 60/60 60/60 44/50 45/50 - - -
15J 3 2 10.8/14.4 36.85/49.13 52/60 73/83 80/80 90/90 65/75 70/80 - - -
20J 4 2 14.4/19.2 49.12/65.52 69.33/80 94/108 100/100 110/110 87/100 90/100 - - -
Unit Min. Ckt
Ampacity @
208-240 V
Heater
A
mp. @ 208
-
240 V
Rated Heater
kW @ 208-
240 V
No. of
Sequence
Steps
A060J
Heater
KBTU/Hr @
208-240 V
A030J
A036J
A042J
A048J
No. of
Elements
Heater Kit
Nominal kW
RXQJ-C
Model
No.
RSNM-
A024J
Heater Kit
Min. Ckt.
Ampacity
Heater Kit
Max. Fuse
Size
Heat Pump
Min. Ckt.
A
mpacity 208
-
240
Heat Pump Over
Current Protective
Device Size
41/41
AUXILIARY ELECTRIC HEATER KITS CHARACTERISTICS AND APPLICATION RSNM