31
EN
2. Parameter lists in KCTR
The full list of parameters is divided into two different menus: “Set Menu” and “Prg Menu”
2.1 Set Menu
Set Menu parameters list:
Par
Icona
Label Description U.M.
Range
Default
min max
405 SEt
Room set point in cooling mode (Comfort temperature)
°C 15 30 24
202 SEt
Room set point in heating mode (Comfort temperature)
°C 5 30 20
201 Att
Attenuation value on Room set point in cooling
mode
°C 1 10 6
203 Att
Attenuation value on Room set point in heating
mode
°C 1 10 4
122 ESA
DHW Production: On: Enabled / Off: Not enabled
- Off On On
126 SEt
DHW Set point (Storage tank)
°C 10 60 50
119 SrH
Room humidity set point
% 30 90 60
108 OUt
Outdoor air temperature
°C -- -
Read
Value
109 OUu
Outlet water temperature from heating pump
°C -- -
Read
Value
111 Inu
Inlet water temperature from heating pump
(see Parameters List on User Manual)
°C -- -
Read
Value