EasyManua.ls Logo

Rievtech xLogic ELC Series - Page 175

Rievtech xLogic ELC Series
393 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
175
e = SP PV
The loop error e brings about a change to the manipulated variable M.
The example above illustrates this very well: if, with a desired temperature of 20 °C (= command value
w), the room temperature is 22 °C (= process value PV), this results in the loop error:
e = SP PV = 20 °C - 22 °C = -2 °C
In this case, the negative sign indicates a reversing action: the heat output is reduced.
In a control loop's state of equilibrium, the loop error is zero or very small. If the command variable
changes or there is a disturbance, a loop error arises. The loop error is corrected by means of the
manipulated variable M.
Controller basics
A controller can be simply portrayed as follows:
The comparing element and the controller function describe the conduct of the controller.
The following describes the most important types of controller. A controller's step response tells us a lot
about its conduct. The step response describes how a controller reacts to the erratic change in the
process value.
There are 3 important basic types of controller:
Proportional-action controller (P controller)
Integral-action controller (I controller)
Differential-action controller (D controller we're not touching on this here)
These are combined for a real controller. For instance, the PI controller:
P Controller
A proportional-action controller (P controller) changes the manipulated variable M proportional to the
loop error. The P controller works immediately. By itself it cannot drive the loop error to zero.
:Manipulated variable of the P controller at the time n
:Gain of the P controller
: Loop error at the time n
The following picture shows a jump in process value and step response of the controller:

Table of Contents