Page #20 background imageLoading...
Page #20 background image
20
008082013GW
Due to insufficient
ionization the burner
has shut down after
ignition
Ionization flow,
ionization cable or
02 setting
Ignition Failure Issue
Flame Failure
Issue
Note: if ionization is lost while the flame is
burning no E02 will occur - unit will attempt to
relight 6 times. E02 only occurs after 6 failed
attempts for re-ignition.
Propane gas with low BTU value or a brand
new tank that may contain something other
than pure propane may cause E02. Check
against a good known source of gas.
The minimum ionization current
should be 4 micro amps (Check
INFO step 48, the O2 should be a
minimum of 4.4% for NG or 4.8%
for LP.
WARNING: Turn off power and water supply to the boiler before removing or installing any parts. If checking
gas pressures you MUST be qualified gas technician to service the gas system on this appliance.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rinnai E- Series and is the answer not in the manual?

Rinnai E- Series Specifications

General IconGeneral
Fuel TypeNatural Gas or Propane
InstallationWall-mounted
TypeCondensing
VentingDirect Vent
DimensionsVaries by model
WeightVaries by model
Warranty12 years heat exchanger, 5 years parts
Heating Capacity15, 000 - 199, 000 BTU/h
Vent TypeDirect Vent