HeatStation™
CONDENSING WATER BOILER
INSTALLATION & MAINTENANCE MANUAL
MODELS HS (1000, 1250, 1500, 1750, 2000)
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND MAINTENANCE
OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED
INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS UNIT.
TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important
information that will help you in maintaining and operating this appliance.
Riverside Hydronics®
3209 Galvez Avenue
Fort Worth, Texas 76111
1-800-990-5918
www.riversidehydronics.com

Table of Contents

Questions and Answers

  • A
    alison03Sep 13, 2025
    What does Hi-Temperature Delta Fault mean for Riverside Hydronics HeatStation HS 1000 Boiler?
    • G
      Gloria BooneSep 13, 2025
      If your Riverside Hydronics Boiler displays a Hi-Temperature Delta Fault, check the pump operation and confirm proper water flow across the heat exchanger.
  • M
    Madison EvansAug 26, 2025
    How to fix Hi-Limit Fault on Riverside Hydronics HeatStation HS 1000 Boiler?
    • D
      Diane JohnsonAug 27, 2025
      If your Riverside Hydronics Boiler displays a Hi-Limit Fault, check for proper water flow and inspect the hi-limit and outlet sensors.
  • H
    hendersonmaryAug 28, 2025
    What to do if Riverside Hydronics HeatStation HS 1000 Boiler shows Sensor Fault?
    • A
      Aaron PaulAug 28, 2025
      If your Riverside Hydronics Boiler has a Sensor Fault, refer to the digital control display to identify the specific fault. Then, inspect the sensors and their wiring.
  • D
    Deborah WellsAug 29, 2025
    How to troubleshoot Low Voltage Fault in Riverside Hydronics Boiler?
    • A
      akellyAug 29, 2025
      If your Riverside Hydronics Boiler shows a Low Voltage Fault, check the 24 VAC input voltage, ensuring it is above 18.0 VAC.
  • M
    Megan SmithAug 31, 2025
    What causes Vent Temperature Fault in Riverside Hydronics Boiler?
    • B
      bradley27Aug 31, 2025
      If your Riverside Hydronics Boiler shows a Vent Temperature Fault, check for a blocked flue and inspect the vent sensor and its connections.
  • H
    Haley GraySep 1, 2025
    Why does Riverside Hydronics Boiler show False Flame Error?
    • J
      Jennifer PerrySep 2, 2025
      If your Riverside Hydronics Boiler displays a False Flame Error, ensure proper gas valve closure and clean the burner and electrodes.
  • S
    Susan CastroNov 22, 2025
    What to do if Riverside Hydronics Boiler has flame failure?
    • M
      Margaret MillerNov 22, 2025
      If your Riverside Hydronics Boiler experiences flame failure, ensure the unit receives 120 VAC for proper operation, investigating any voltage below 110 VAC. Check the hot surface igniter's resistance at room temperature and amperage draw during heat-up; replace if amperage isn't within 3.5 to 5.0 Amps or resistance isn't within 40-100 ohms (at room temperature), and inspect for overheating due to damaged refractory. Verify the blocked vent switch isn't bouncing; adjust or replace if necessary. Confirm proper inlet static and dynamic gas pressure, ensuring it's between 3.5" WC minimum and 14" WC maximum. Adjust combustion to achieve proper CO2 levels. Ensure a proper ground connection from the flame control to the burner housing. Lastly, check that the condensate trap isn't blocked, causin...
  • Y
    ykelleySep 15, 2025
    How to fix ID Card Fault on Riverside Hydronics HeatStation HS 1000?
    • B
      browndannySep 15, 2025
      If your Riverside Hydronics Boiler displays an ID Card Fault, check that the proper ID card is securely connected and perform a power and system reset.
  • A
    Adrienne MillerSep 12, 2025
    What to do if Riverside Hydronics HeatStation HS 1000 has LWCO Fault?
    • C
      Carolyn TannerSep 12, 2025
      If your Riverside Hydronics Boiler displays an LWCO Fault, check the LWCO switch and connections, and verify the water level.
  • E
    Edward BrowningSep 8, 2025
    How to troubleshoot Water Pressure Fault in Riverside Hydronics Boiler?
    • A
      Alexandra OrtegaSep 8, 2025
      If your Riverside Hydronics Boiler displays a Water Pressure Fault, check the piping for leaks and inspect the pressure switch and its connections.

Riverside Hydronics HeatStation HS 1000 Specifications

General IconGeneral
BrandRiverside Hydronics
ModelHeatStation HS 1000
CategoryBoiler
LanguageEnglish