How to troubleshoot a starting or pre-purge failure in Riverside Hydronics Boiler?
- MMatthew NunezNov 10, 2025
If your Riverside Hydronics Boiler fails to start or pre-purge, here's what you can check: * **Power Supply:** Verify the fuse and/or circuit breaker. Also, check the voltage at the 120/24V step-down transformer. * **On-Off Switch:** Make sure the On-Off switch is illuminated. * **Temperature Control:** Ensure the operating temperature control is set higher than the boiler's current temperature. * **Flame Safeguard Control:** Check for a bad ground or a faulty control; replace if needed. * **Remote enable/disable open:** Enable the boiler or place a jumper between terminals R1-R2. * **Combustion Air blower:** Confirm the fan connection terminals on the flame control are closed and check for 24V at field access terminal C2. The remote interlock may be open. Also, the fan VFD ma...