WATER BOILER
INSTALLATION & MAINTENANCE MANUAL
Models (400, 500, 650, 750, 850, 900 and 1000) WB 125A-IF
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND MAINTENANCE
OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED
INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS UNIT.
TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important
information that will help you in maintaining and operating this appliance.
Riverside Hydronics
®
, LLC
990 Haltom Road
Fort Worth, Texas 76117
1-800-990-5918
www.riversidehydronics.com

Table of Contents

Questions and Answers

  • T
    Tina WilsonAug 11, 2025
    What to do if Riverside Hydronics Boiler has flame failure?
    • N
      Nicholas FoxAug 11, 2025
      If your Riverside Hydronics Boiler experiences flame failure, start by checking the fuse and circuit breaker, and ensure the voltage at the 120/24V step-down transformer is correct. Inspect the flame safeguard control for any grounding issues or defects, and replace if necessary. Also, verify that all safety limits are functioning correctly and address any fault conditions. Check the grounding from the flame control to the burner housing.
  • N
    Nicole PierceAug 20, 2025
    Why is my Riverside Hydronics VT.3 400 WB 125A-IF failing to start or pre-purge?
    • C
      Cameron RodgersAug 20, 2025
      If your Riverside Hydronics Boiler fails to start or pre-purge, check the fuse and circuit breaker, and ensure the voltage at the 120/24V step-down transformer is correct. Verify that the on-off switch is lit and the operating temperature control is set higher than the boiler temperature. Inspect the flame safeguard control for bad ground or defects, replacing it if needed. Confirm the boiler is enabled or place a jumper between terminals R1-R2, and check that the fan connection terminals on the flame control are closed. Also, check the connections to all components.
  • J
    Joseph Rivera Jr.Aug 30, 2025
    How to troubleshoot flame failure in Riverside Hydronics Boiler?
    • S
      Sarah SandovalAug 30, 2025
      If your Riverside Hydronics Boiler is experiencing flame failure, there are several potential causes: * **Hot Surface Igniter:** Check the amp draw during heat-up. Replace if amps are greater than 3.1A. Also, look for signs of overheating due to damaged refractory around the igniter. * **Air-Proving Switch:** Check if the switch is bouncing; if so, adjust or replace it. * **Gas Pressure:** Verify proper inlet static and dynamic gas pressure. * **Combustion:** Inadequate flame signal may result from improper combustion. Adjust to proper CO2 levels at low fire.

Riverside Hydronics VT.3 400 WB 125A-IF Specifications

General IconGeneral
CategoryBoiler
ModelVT.3 400 WB 125A-IF
Efficiency85%
Fuel TypeNatural Gas
Operating Pressure125 psi
Heating Capacity400, 000 BTU/hr