The Technical Specifications of the Tests performed by the SmartPAT 5500 Portable Appliance Tester are
as follows:
Earth Bond
The earth bonding specifications are taken at a nominal mains input supply of 110 V or 235 V rms, unless
otherwise stated.
High Current
Open Circuit Voltage 3 V rms ±10%
Test Current 5 A, 8 A or 26 A ±15% into 0.1 ohm load.
(in-built intelligent current limit)
Display Resolution 0.01 ohm to 19.99 ohm, then shows >20 ohm.
Display Accuracy ±(3% + 4 digits)
Test Duration 10s or 15s to 1 minute, dependent on time test button held down
Business Equipment
Open Circuit Voltage 3 V rms ±10%
Test Current 100 mA +20% -0% at 230 Vrms into 0.5 ohm load.
Display Resolution 0.01 ohm to 19.99 ohm, then shows >20 ohm.
Display Accuracy ±(3% + 4 digits)
Test Duration 10s or 15s to 1 minute, dependent on time test button held down
Pass Threshold 0.1 ohm steps up to 5 ohm then 0.5 ohm steps to 19.99 ohm
(user selectable)
Insulation Test
The earth bonding specifications are taken at a nominal mains input supply of 110 V or 235 V rms, unless
otherwise stated.
Open Circuit Voltage 560 V dc +16%, -0%
Short Circuit Current 3.5 mA ±10%
Current into 500k 1.0 mA minimum
Display Resolution 0 1 to 99.9 Mohm, then 1 to 299 Mohm, >300 Mohm
Display Accuracy ±(5% + 4 digits)
Test Duration 10s or 15s to 1 minute, dependent on time test button held down
Pass Threshold 0.1 Mohm steps to 0.9 Mohm
1 Mohm steps from 1 to 9 Mohm
10 Mohm steps from 10 to 300 Mohm
(user selectable)
Fuse/Load/Leakage Test
Leak
Earth Leakage Current 0.1mA to 9.9mA
Display resolution 0.1mA
Display accuracy ±(5% + 4 digits), capacitive/resistive leakage
Leakage threshold 0.5 to 10 mA in 0.5 mA steps
Abort on leakage > 15 mA
4