20 ControlLogix Power Supplies
Publication 1756-IN613A-EN-P - December 2008
Nonoperating
temperature
IEC 60068-2-1 (Test
Ab, Unpackaged
Nonoperating Cold)
IEC 60068-2-2 (Test
Bb, Unpackaged
Nonoperating Dry
Heat)
IEC 60068-2-14 (Test
Na, Unpackaged
Nonoperating Thermal
Shock)
-40…85 °C (-40…185 °F)
Relative humidity
IEC 60068-2-30 (Test
Db, Unpackaged
Nonoperating Damp
Heat)
5…95% noncondensing
Vibration
IEC 60068-2-6 (Test
Fc, Operating)
2 g @ 10…500 Hz
Operating shock
IEC 60068-2-27 (Test
Ea, Unpackaged
Shock)
30 g
Nonoperating shock
IEC 60068-2-27 (Test
Ea, Unpackaged
Shock)
50 g
ESD immunity
IEC 61000-4-2
6 kV contact discharges
8 kV air discharges
Emissions
CISPR 11
Group 1, Class A
1756-PB72 Series C, 1756-PB75 Series B, 1756-PC75 Series B, 1756-PH75 Series B -
Environmental Specifications
Attribute 1756-PB72
Series C
1756-PB75
Series B
1756-PC75
Series B
1756-PH75
Series B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Rockwell Automation ControlLogix 1756-PA72 Series C and is the answer not in the manual?

Rockwell Automation ControlLogix 1756-PA72 Series C Specifications

General IconGeneral
BrandRockwell Automation
ModelControlLogix 1756-PA72 Series C
CategoryPower Supply
LanguageEnglish

Related product manuals