Installation manual
7
RKRTW
Room thermostat
4PW50082-1
Temperature control codes
Rotex advizes not to change below temperature control
parameters. They are set for an optimal use of the floor cooling/
heating application.
6® 02
Use
proportional
band control?
ÚêÒ ÚêÒ
(proportional
band)
/≈œ
(hysteresis)
—
03
Hysteresis
value
00.5 00.5~02.0
0.1°C
04 + p
Duration
proportional
band (heating).
020 010~060
1 min.
05 + p
Minimum "on"
time (heat
demand).
007 002~ 6® 04/2
1 min.
06 + p
Minimum delay
between 2
heating cycles.
003 001~ 6® 04/2
1 min.
07 + o
Duration
proportional
band (cooling).
020 010~060
1 min.
08 + o
Minimum "on"
time (cool
demand).
007 002~ 6® 07/2
1 min.
09 + o
Minimum delay
between 2
cooling cycles.
003 001~ 6® 07/2
1 min.
10
Value of
proportional
band.
02.0 01.0~04.0
0.1°C
11
Compensating
value.
00.0 00.0~08.0
0.1°C
1st
code
2nd
code
Description Default Range Step
1O_IM_4PW50082-1.book Page 7 Monday, October 20, 2008 9:15 AM