20 
room of at least 10 cm around the router.   
  Do not place any heavy things on the router. 
2.2.4  Performing EMC Grounding 
The grounding required for EMC design includes the shielding ground, filter ground, noise and interference 
suppression, and level reference, which constitute the comprehensive grounding requirements. The grounding 
resistance should be less than 1 ohm. The RG-NBR-E series routers are equipped with a grounding pole at the 
rear panel, as shown in Figure 2-1 and Figure 2-2. 
Figure 2-1  Grounding of the RG-NBR-E Series Routers 
 
 
Figure 2-2  Grounding of RG-NBR6205-E, RG-NBR6210-E, and RG-NBR6215-E Series Routers 
 
Grounding steps are as follows: 
(1)  Connect the grounding screw of the device to the grounding terminal of the cabinet or workbench using the 
grounding wire. 
(2)   Connect the grounding terminal of the cabinet or workbench to the grounding bar of the equipment room. 
2.2.5  Installing the Power Cord 
The requirements of Ruijie RG-NBR-E series Routers on AC power supply are 100–240 V and 50/60 Hz.   
The Router  uses  3-conductor power cords.  You  are advised to  use  a single-phase 3-conductor  outlet or a 
multifunction microcomputer outlet with the neutral connector. The neutral point of the power supply should be 
securely grounded in the building. In most buildings, the neutral point of a power supply has been grounded 
during the construction. Ensure that the power supply is properly grounded. 
Plug one end of the power cord into the power port on the back panel of the Router, and the other end into the 
AC power supply outlet. 
 
Caution 
Make sure that the main power supply is off before inserting the power plug.