5. AUXILIARY
5. AUXILIARY
FUNCTIONS
FUNCTIONS
MENU
MENU
5.3 MENU DESCRIPTION
5.3 MENU DESCRIPTION
What you see
on the display
DescripƟon and Comments
Normal
Mode
Insp
Mode
Visibility
Condition
Range
Default
Value
V4.00.K Firmware version + revision number V V
Normal
FLxx
Li/Door Status + Floor number V V
View Faults
(Fatal=--)
View faults log If faults exist
Homing trip? Request a homing trip V V
Simplex(1)Full
Swinging
Li summary V V
Simulate calls On-board calls registration
V/A
NV
/
NA
Inspecon
operaon
On-board inspecon operaon
NV/
NA
V/A
Boards detected
On Bus
Used in group mode
DT is
connected
Enter Password Access the menu V/A V/A
Empty Fault Log Clears the fault log if faults exist
Light Time Car light turn o delay in sec A A N/A 5 to 99” 10”
Floor Stopping
Time
Time between travel in sec A A N/A 1.0 to 9.9” 3.0”
Parking Door The parking status of the door A A Auto/Half Auto door Opened/Closed Closed
Door
Nudging/Obst
When enabled, the
RE OPN
input is
bypassed to clear any obstacle blocking
the door/ When disabled and the door is
held open, it is considered to be
obstructed aer this delay
A A N/A Ena/ Dis, 5 to 99” Dis, 90”
Hydraulic Star
Time
Star starting time of the hydraulic pump A A Hydraulic elevator 0.0 to 9.9” 1.0”
VVVF Start
Delay
The delay in sec between providing
direcon and speed reference outputs
A A VVVF drive -9.9 to 9.9” 0.0”
VVVF/ Hyd Stop
Delay
The delay in sec between removing
direcon and speed reference outputs
A A VVVF drive/Hydraulic -9.9 to 9.9” 3.0”
Gong Time The gong me in seconds A A
Spare1 or Spare2 or
Spare3 or Spare4
funcon=gong, CC+,
CC-, HC+, HC-
0.0 to 7.5” 3.0”
Minimum Load
When this feature is enabled, car calls are
canceled if car stops twice on a car call
and no passengers exit car
A A N/A Disabled/Enabled Disabled
Main Landing
Sets the landing oor along with the delay
before making a main landing trip given
that the elevator has no calls to serve
A A N/A
None, 0… 31- 0’10” to
30’59”
None
Power On
Homing
When enabled, the elevator makes a
homing trip upon every power-on
When disabled following power on and if
li is not parked on a oor , the controller
will take it to the nearest oor traveling in
the same direcon prior to power failure
When set to NoDZ and the li is on a
oor, no action is taken. Otherwise, li
will do homing trip upon power-on
A A N/A Disabled/Enabled/ NoDZ Disabled
V means visible
A means accessible
NV means not visible
NA means not accessible
If there are 2 close oors or the elevator slips more than ½ distance of the oor, “Power On Homing” must be set to enabled
18