5. AUXILIARY
5. AUXILIARY
FUNCTIONS
FUNCTIONS
MENU
MENU
What you see
on the display
DescripƟon and Comments
Normal
Mode
Insp
Mode
Visibility
Condition
Range
Default
Value
Permanent
Close
When this feature is enabled, the door
closing signal is permanently engaged
during travel (required for specific types
of door drives)
A A Automac door Disabled/Enabled Disabled
Permanent
Open
When this feature is enabled, the door
opening signal is permanently engaged
when the door is totally opened
A A Automac door Disabled/Enabled Disabled
RE-OPN i/p Sets the logic of the re-opn input A A N/A no/nc nc
Reset me on
re-opn
When this feature is set to Y and the door
is counng Floor Stopping Time to start
closing, Then if the photocell is cut,
Restart counng Floor Stopping Time
A A Auto/½ Auto door N/Y N
Door Zone
When this feature is installed, the
controller looks for the DZ magnec
switch signal upon every oor stop. The
absence of this signal on oor level
prompts the
controller to register a Level II fault and to
perform a homing trip
NA A N/A None/Installed None
Pre-opening
When this feature is enabled, door starts
opening when DZ is reached
A A DZ installed Disabled / Enabled Disabled
First Stop
Selects the gray code output for the rst
stop
A A N/A 0 / 1 0
Collecve
Selects between collecve selective, down
collecve and mulplexing modes
NA A N/A
Full / Down / APB /Mul/
MulF
Down
Carcall priority Gives priority to car calls over hall calls NA A Collecve#APB N/Y N
Encoder
Set to installed to implement direct
approach
NA A
VVVF Drive & Door
Zone installed
None / Installed None
Pulses/Revolu
on
Sets the count of pulses per revoluon of
the incremental encoder
NA A Encoder installed 0 to 9999 1024
Roping Selects the roping ratio of the installaon NA A Encoder installed 1:1, 2:1 or 4:1 1:1
Nominal RPM Nominal RPM of machine NA A Encoder installed 0 to 9999 1500
Machine speed
m/s
Sets the speed of the machine NA A Encoder installed 0 to 9.999 2.000
HiSpd reached
(m)
Distance traveled to accelerate from zero
to high speed
NA A Encoder installed 0 to 9.999 3.500
IntSpd reached
(m)
Distance traveled to accelerate from zero
to intermediate speed
NA A Encoder installed 0 to 9.999 1.400
LoSpd reached Distance traveled to accelerate from zero
to low speed
NA A Encoder installed 0 to 9.999 0.060
RllSpd reached
(m)
Distance traveled to accelerate from zero
to re-leveling speed
NA A
Encoder installed &
Re-leveling not
Disabled
0 to 9.999 0.030
SlowDown dist.
m
Distance traveled to decelerate from high
speed to zero
NA A Encoder installed 0 to 9.999 3.500
Int. SlowDown
m
Distance traveled to decelerate from
intermediate speed to zero
NA A Encoder installed 0 to 9.999 1.400
Lo SlowDown m
Distance traveled to decelerate from low
speed to zero
NA A Encoder installed 0 to 9.999 0.060
Relevel
SlowDown m
Distance traveled to decelerate from re-
leveling speed to zero
NA A
Encoder installed &
Re-leveling not
Disabled
0 to 9.999 0.030
Extension
Boards
Sets the count of extension boards
installed and thus the distribuon of the
car and land calls
NA A N/A None, 1, 2 or 3 None
Mode
Selects between simplex and group
modes.
NA A N/A Simplex/Group Simplex
Multiplexing mode cannot be used in group mode
means not accessible
A means accessible
N/A means not assigned