6.2 Dual Inverter System Diagnostics / Fault detection.
Sygnal systems are able to detect a number of problems and display a fault message to aid in troubleshooting.
If any fault messages are displayed contact your installer/service person.
Fault I1 Indoor and Outdoor unit not compatible
Line1 = Fault I1:
Line 2 scrolls one of the following:
AHU and Condenser not compatible
Fault I2 Coil Sensor Error (sensor nominated)
Line 1 = Fault I2:
Line 2 scrolls the following:
Outdoor coil sensor open circuit
Outdoor coil sensor short circuit
Indoor coil sensor open circuit
Indoor coil sensor short circuit
Fault I3 Contact Manufacturer
Line 2 scrolls one of the following:
Contact Manufacturer
Fault I4 Interconnect Indoor>Outdoor
Line 1 = Fault 4:
Line 2 scrolls one of the following:
AHU and Condenser Interconnect
Fault I5 Contact Manufacturer
Line 1 = Fault 5:
Line 2 scrolls Contact Manufacturer
Fault I6 Contact Manufacturer
Line 1 = Fault 6:
Line 2 scrolls Contact Manufacturer
Fault I7 Zoning to Indoor Board Communications Lost
Line 1 = Fault I7:
Line 2 scrolls AHU and Zoning interconnect
Fault I8 Contact Manufacturer
Line 1 = Contact Manufacturer