6.4.3. “DX_coolOff” – chlorouorocarbon cooling is switched
off at “Cool PI”, % (*20%)
6.4.4. “OutDoor T.C” – when outdoor air temperature ex-
ceeds this setting, cooling is allowed, 10-30°C (*12°C)
6.5. “Add.Func.”
6.5.1. “Night Cool” – night cooling „On/*Off“
6.5.2. “CO2” – highest allowed level of CO2. If exceeded, the
supply air ow is increased, %, *550ppm
6.5.3. “Fast Butt.” – select the function of the fast button:
“Standby( Sleep)” – the unit switches to standby
mode. It will enter into operation after permitted turn off
time or when the night cooling function will turn on.
“Boost/replace”- settings of „Boost/replace“ function
(see. 6.6. )
“Off” – fast button function off.
6.5.4. “FanStopTime” – time for cooling of the electrical
heater after switching the unit off, 0-255 s. (*60s.)
6.6. “Boost Ctrl.”
6.6.1. “Boost timer” – “Boost/replace” operation period of
the function, *0-255 min.
6.6.2. “Boost SAF” – supply air fan speed during operation
of the “Boost” function, %, Pa
6.6.3. “Boost EAF” – extracted air fan speed during opera-
tion of the “Boost” function, %, Pa
6.7. “SAF Ctrl.” – supply fan speed or pressure setting (depends
on conguration).
6.7.1. “SAF Low” – set supply fan speed “Low”, %, Pa
6.7.2. “SAF Midd” – set supply fan speed “Middle” “, %, Pa
6.7.3. “SAF High” – set supply fan speed “High”, %, Pa
6.8. “EAF Ctrl.” – extraction fan speed or pressure setting (de-
pends on conguration)
6.8.1. “EAF Low” – set extraction fan speed “Low”, %, Pa
6.8.2. “EAF Midd” – set extraction fan speed “Middle” “,
%, Pa
6.8.3. “EAF High” – set extraction fan speed “High”, %, Pa
6.9. “Versions” – version of the unit software, board, settings are
shown; when “OK” is pressed, panel version and software
date is shown. Return to menu by pressing “ ”.
6.10. “Service” – additional options of the unit’s settings (see “Serv-
ice instructions”).
6.11. “Filters“- lter contamination-hours timer is activated in serv-
ice menu “Misc” –“> F Timer”.
6.11.1. “Set Timer” – the operation time for the unit is set until
contamination of the lters will be reported.
6.11.2. “ReSet Timer” – zero adjustment of the timer
6.11.3. “Curr.Timer”– current number of working hours
7. “Menu conguration”
Extra settings: (see.: Service instruction 17.1.)