10 | EN SMARTY v2023.2
4.3. TECHNICAL DATA
SMARTY 2X P 1.1 2X P 1.2
2X P
S300 3X P 1.1 3X P 1.2
3X P
S300
4X P F2
1.1
4X P F2
1.2
4X P
S300
Exhaust air fan
phase/voltage [50 Hz/VAC] 1/230 1/230 1/230
power/current [kW/A] 0,05/0,4 0,09/0,75 0,17/1,35
speed [min
-1
] 4525 3200 4120
control input [VDC] 0-10 0-10 0-10
protection class IP44 IP54 IP54
Supply air fan
phase/voltage [50 Hz/VAC] 1/230 1/230 1/230
power/current [kW/A] 0,05/0,4 0,09/0,75 0,17/1,35
speed [min
-1
] 4525 3200 4120
control input [VDC] 0-10 0-10 0-10
protection class IP44 IP54 IP54
Total power/current con-
sumption
[kW/A] 0,16/1,05 0,16/1,05 0,15/1,02 0,23/1,75 0,23/1,75 0,23/1,7 0,4/2,95 0,4/2,95 0,39/2,92
Automatic control integrated miniMCB
miniMCB
basic
S300 miniMCB
miniMCB
basic
S300 miniMCB
miniMCB
basic
S300
Insulation of walls [mm] 20 30 30
Exhaust air lter (class,
dimensions LxWxH)
[mm] MPL 185x168x25 Coarse 65% MPL 225x195x25 Coarse 65% MPL 225x195x25 Coarse 65%
Supply air lter (class,
dimensions LxWxH)
[mm] MPL 185x168x25 Coarse 65% MPL 225x195x25 Coarse 65% MPL 225x195x25 Coarse 65%
Device protection class IP-34 IP-34 IP-34
SMARTY 2X V 1.1 2X V 1.2
2X V
S300 3X V 1.1 3X V 1.2
3X V
S300
4X V F2
1.1
4X V F2
1.2
4X V
S300
Exhaust air fan
phase/voltage [50 Hz/VAC] 1/230 1/230 1/230
power/current [kW/A] 0,04/0,35 0,08/0,75 0,17/1,35
speed [min
-1
] 4060 3200 4120 4600
control input [VDC] 0-10 0-10 0-10
protection class IP54 IP54 IP54
Supply air fan
phase/voltage [50 Hz/VAC] 1/230 1/230 1/230
power/current [kW/A] 0,04/0,35 0,08/0,75 0,17/1,35
speed [min
-1
] 4060 3200 4120 4600
control input [VDC] 0-10 0-10 0-10
protection class IP54 IP54 IP54
Integrated electrical
preheater
[kW] 0,6 - - 1,2 -
-
1,2 - -
Total power/current con-
sumption
[kW/A] 0,74/3,62 0,14/0,95 0,13/0,92 1,43/7 0,23/1,75 0,23/1,7 1,6/8,15 0,4/2,95 0,39/2,92
Automatic control integrated miniMCB
miniMCB
basic
S300 miniMCB
miniMCB
basic
S300 miniMCB
miniMCB
basic
S300
Insulation of walls [mm] 30 30 30
Exhaust air lter
(class, dimensions
LxWxH)
[mm] MPL 270x187x25 Coarse 65% MPL 475x180x25 Coarse 65% MPL 475x180x25 Coarse 65%
Supply air lter
(class, dimensions
LxWxH)
[mm] MPL 270x121x25 Coarse 65% MPL 475x134x25 Coarse 65% MPL 475x134x25 Coarse 65%
Device protection class IP-34 IP-34 IP 34
According to EN 13141-7.
Acoustic data: check the product page on www.salda.lt
Not suitable for installation in living rooms: additional noise insulation required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Salda Smarty 2X P 1.2 and is the answer not in the manual?

Salda Smarty 2X P 1.2 Specifications

General IconGeneral
BrandSalda
ModelSmarty 2X P 1.2
CategoryAir Handlers
LanguageEnglish

Related product manuals