EasyManua.ls Logo

Salus EVT7EU - Page 30

Salus EVT7EU
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
30
PEN fault protection for EVT7UK : 7kW (1-phase) tethered
type (UK version)
When installed on a PME electrical system it is necessary to protect the user from a potential
electric shock that could occur if the combined Neutral and Earth (PEN) conductor on the supply
becomes damaged or disconnected.
EVT7UK model has an in-built PEN fault protection function, as described in BS 7671 Clause
722.411.4.1 (iv), to disconnect the vehicle from the live, neutral and earth conductors if the
voltage is above or below the prescribed levels (greater than 253V and less than 207V). It
removes the need for an additional earth electrode or earth rod installation.
Account sign off & Factory reset
When removing the EV charger from your account, the EV charger will also perform
a factory reset.
Once nished, the LED on
the charger ashes Yellow.
Account Sign Off & Factory Reset