4.5 GROUP 2 PARAMETER SET UP: INPUT SETTING
4.5.1 Programming Ranges & Default Values of Programming Parameters under Parameter Group
2 – INPUT SETTING
Table 4.6 gives details of programming ranges & default values of parameters under Parameter Group No.2 - "INPUT SETTING".
Refer to Fig 4.3 under Section 4.1.3.2 for Menu Map for navigating through various parameters under this Group No.2.
TABLE 4.6 Programming Information for Parameter Group No.2 - INPUT SETTING (Refer to Menu Map at Fig 4.3, Section 4.1.3.2)
Parameter Setup
Screen Nos. for:
EVO-1212F
EVO-1212F-HW
EVO-1224F
EVO-1224F-HW
(Column 1)
Parameter Setup
Screen Nos. for:
EVO-2212
EVO-3012
EVO-2224
EVO-4024
(Column 2)
Parameter
(Column 3)
Setting range
EVO-1212F
EVO-1212F-HW
(Column 4)
EVO-
2212
(Column 5)
EVO-
3012
(Column 6)
EVO-1224F
EVO-1224F-HW
(Column 7)
EVO-
2224
(Column 8)
EVO-
4024
(Column 9)
1 1
DEFAULT FREQ
See NOTE
0=60Hz;
(Default:
60Hz)
0=60Hz; 1=50Hz
(Default: 60Hz)
See NOTE
0=60Hz;
(Default:
60Hz)
0=60Hz; 1=50Hz
(60Hz)
2 2
GRID MAX CURRENT
5 – 20A
(Default: 20A)
5 – 40A
(Default:30A)
5 – 70A
(Default:30A)
5 – 20A
(Default: 20A)
5 – 40A
(30A)
5 – 70A
(30A)
- 3
GEN MAX CURRENT
5 – 40A
(Default:30A)
5 – 70A
(Default:30A)
5 – 40A
(30A)
5 – 70A
(30A)
3 4
HIGH CUT OFF
50 – 70Hz
(Default: 65Hz)
4 5
HIGH RESET
50 – 70Hz
(Default: 64Hz)
5 6
LOW CUT OFF
40 – 60Hz
(Default: 55Hz)
6 7
LOW RESET
40 – 60Hz
(56Hz)
7 –
SYNCHRONIZATION
0=Fine
(Default)
1=Coarse
0=Fine
(Default)
1=Coarse
– 8
SYNC GRID
0=Fine (Default)
1=Coarse
0=Fine (Default)
1=Coarse
– 9
SYNC GEN
1=Coarse (Default)
0=Fine
1=Coarse (Default)
0=Fine
8 10
INPUT OC PROTECT
0=INV mode (Default)
1=Shutdown
9 11
INPUT RECOVERY
0=Buffered (Default)
1=Direct
NOTES for Table 4.6:
1. DEFAULT FREQ parameter is xed al 60Hz for EVO-1212F / 1212F-HW and EVO-1224F / 1224F-HW (Option
0=60Hz). If option 1 is entered, the screen line will show "! 1=xxHz" meaning that Option 1 is invalid.
2. Parameter "GEN MAX CURRENT" is not available for EVO-1212F / 1212F-HW and
EVO-1224F / 1224F-HW as separate Generator input is not available in these models.