EasyManua.ls Logo

Samlexpower EVO-RC-PLUS - Page 75

Samlexpower EVO-RC-PLUS
112 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SAMLEX AMERICA INC. | 75
SECTION 4 | Parameter Setup
ii. Then, the phase of the Inverter voltage relative to the phase of the Grid / Inverter Generator
voltage is tracked by 1º per cycle. When the phase of the Inverter voltage is within ± 3.5º of
the input voltage waveform, the Transfer Relay is activated to transfer the AC load from the
Grid / Inverter Generator to the Inverter Section at zero crossing of the voltage waveform.
4.5.2.10.1 Programming Steps for Parameter “SYNC GEN”
ð ð
E V O - 1 2 1 2 F I n v e r t i n g
A C o u t p u t : 1 2 0 . 0 V
< 0 . 1 0 A
6 0 . 0 0 H z
Enter Key
Down Key x 8 times for
EVO-2212/3012/2224/4024
Any Operating Mode Screen from
Fig 3.1 to 3.5
[Above screen is Screen 1 of Fig 3.2(a)]
Password 8052
See Section 4.3.1
For programmable options, see Table 4.6,
Parameter Setup Screen No. 9 under
Column 2 for EVO-2212/3012/2224/4024
S e l e c t G r o u p
* C H A R G E C U R V E
ð
S e l e c t P a r a m e t e r
* I N P U T S E T T I N G
ð
S e l e c t P a r a m e t e r
I N P U T S E T T I N G
* D E F A U L T F R E Q
0 = 6 0 H z
S e l e c t P a r a m e t e r
I N P U T S E T T I N G
* S Y N C G E N
0 = F i n e
Down Key x 1 time
Enter Key
P a s s w o r d k e y i n
0 0 0 0
ð
Enter Key
S e l e c t P a r a m e t e r
I N P U T S E T T I N G
* S Y N C G E N
0 = F i n e
ð
Enter Key
4.5.2.11 INPUT OC PROTECT
(Table 4.6: (i) Parameter Setup Screen No.8 under Column 1 for EVO-1212F/1212F-HW/1224F/1224F-HW
(ii) Parameter Setup Screen No.10 under Column 2 for EVO-2212/3012/2224/4024)
If the net AC input current is 1A more than the value of GRID MAX CURRENT (See Section 4.5.2.2) or GEN MAX
CURRENT (See Section 4.5.2.3) for 1 sec, the AC side charging current is clawed back to ensure that GRID MAX
CURRENT / GEN MAX CURRENT value is not exceeded. If the value of pass through load current increases to a value
of 1A more than the programmed value of GRID MAX CURRENT / GEN MAX CURRENT for 5 sec, input over current
protection will be activated based on the following 2 options provided through parameter INPUT OC PROTECT:
a) Option "0=INV mode" (Default Option). Set up screen is shown below:
S e l e c t P a r a m e t e r
I N P U T S E T T I N G
* I N P U T O C P R O T E C T
0 = I N V m o d e
o If the AC input current is 1A more than the programmed value of GRID MAX CURRENT / GEN MAX
CURRENT for more than 5 sec, the unit will switch over to Inverter Mode to ensure that AC power to
the load is maintained.
o If the load reduces to 1A less than the programmed value of GRID MAX CURRENT / GEN MAX
CURRENT for 5 sec, switch back to Charging Mode
b) Option "1=Shutdown" (Default Option). Set up screen is shown below:
S e l e c t P a r a m e t e r
I N P U T S E T T I N G
* I N P U T O C P R O T E C T
1 = S h u t d o w n
o If the AC input current is 1A more than the programmed value of GRID MAX CURRENT / GEN MAX
CURRENT for more than 5 sec, Fault Mode will be activated:
There will be no AC output because the Transfer Relay will be de-energized, charging will be stopped
and PWM drive to the Inverter Section will be switched off

Related product manuals