26
Wiring Work
Installation
Communication wiring connections
Communication wires connect through side of air handler.
Use an approved connector at the cabinet of the unit to prevent pulling or shorting of control wires.
ATTENTION
Control wire must be rated for 600V minimum.
Control wire insulation must be rated for temperatures up to 90°C.
1. Insert the wires through the holes of the right side on the top casing and through the cable connectors.
2. Connect the communication wires to the F1/F2 connection terminal with compressed ring terminals.
3. Connect F3, F4 (for communication) when installing the wired remote control.
PBA ground screw/connection to chassis
1(L)/2(N) high voltage connection terminals
F1/F2 communication connection terminals
Supply power ground connection point
Selecting compressed ring terminal
Silver solder
Nominal
dimensions
for cable
[inch
2
(mm
2
)]
Nominal
dimensions
for screw
[inch(mm)]
B D d1 E F L d2 t
Standard
dimension
[inch(mm)]
Allowance
[inch(mm)]
Standard
dimension
[inch(mm)]
Allowance
[inch(mm)]
Standard
dimension
[inch(mm)]
Allowance
[inch(mm)]
Min.
[inch(mm)]
Min.
[inch(mm)]
Max.
[inch(mm)]
Standard
dimension
[inch(mm)]
Allowance
[inch(mm)]
Min.
[inch(mm)]
0.0023
(1.5)
0.16(4) 0.26(6.6)
±0.0079
(±0.2)
0.13(3.4)
+0.012(+0.3)
-0.0079
(-0.2)
0.067(1.7)
±0.0079
(±0.2)
0.16(4.1) 0.24(6.0) 0.63(16.0) 0.17(4.3)
+0.0079
(+0.2)
0(0)
+0.0079
(+0.2)
0(0)
0.16(4) 0.31(8.0)
0.0039
(2.5)
0.16(4) 0.26(6.6)
±0.0079
(±0.2)
0.17(4.2)
+0.012(+0.3)
-0.0079
(-0.2)
0.091(2.3)
±0.0079
(±0.2)
0.24(6.0) 0.24(6.0) 0.69(17.5) 0.17(4.3)
+0.0079
(+0.2)
0(0)
+0.0079
(+0.2)
0(0)
0.16(4) 0.33(8.5)
0.0062
(4.0)
0.16(4.0) 0.37(9.5)
±0.0079
(±0.2)
0.22(5.6)
+0.012(+0.3)
-0.0079
(-0.2)
0.134(3.4)
±0.0079
(±0.2)
0.24(6.0) 0.24(6.0) 0.79(20.0) 0.17(4.3)
+0.0079
(+0.2)
0(0)
+0.0079
(+0.2)
0(0)
DB68-11271A-02_IM_CAC Universal AHU Indoor_AA_EN_.indd 26 2022-09-15 오전 9:53:20