English
Blower CFM tables
Installation
AC024BNZDCH
HP : 1/3 Default motor taps : High/Mid/Low = 4/3/2.
Motor Tap P(inwg) CFM Motor Tap P(inwg) CFM
1
0.1 543
4
0.1 811
0.2 512 0.2 810
0.3 479 0.3 797
0.4 446 0.4 773
0.5 411 0.5 737
0.6 374 0.6 689
0.7 337 0.7 630
0.8 298 0.8 559
2
0.1 564
5
0.1 894
0.2 542 0.2 890
0.3 518 0.3 870
0.4 492 0.4 837
0.5 464 0.5 789
0.6 433 0.6 726
0.7 400 0.7 649
0.8 366 0.8 558
3
0.1 669
0.2 649
0.3 628
0.4 606
0.5 582
0.6 559
0.7 534
0.8 508
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
200 300 400 500 600 700 800 900 1000
Q (CFM)
1
2
3
4
5
P (inwg)