54
Installation Procedure
Installation
Option SEG 13 SEG 14 SEG 15 SEG 16 SEG 17 SEG 18
Function Page Use of external control
Setting the output
of extermal control
Reserved
Buzzer control
Maximum lter
usage time
2)
Indication
and
details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
2
0 Disuse
Sub,
Existing
control
0
Thermo
on
0
Use of
buzzer
2
1000
hours
1 On/Off
2 Off
3
Window
On/Off
4 Disuse
Main,
Existing
control
5 On/Off
6 Off
7
Window
On/Off
8 Disuse
Sub,
Reverse
control
1
Operation
On
1
Disuse of
buzzer
6
2000
hours
9 On/Off
A Off
B
Window
On/Off
C Disuse
Main,
Reverse
control
D On/Off
E Off
F
Window
On/Off
Option SEG 19 SEG 20 SEG 21 SEG 22 SEG 23 SEG 24
Function
Page
Individual control
with remote
control
3)
Heating setting
compensation
4)
Reserved
Reserved
Reserved
Indication
and
details
Indication
Details
Indication
Details
Indication
Details
3
0, 1 Indoor1 0 Default
2 Indoor2
1
3 Indoor3
4 Indoor4 2
1)
SEG4
By SEG4 setting, Minimizing fan operation when thermostat is off.
Fan operates for 20 seconds at an interval of 5 minutes in heat mode.
Fan stops or operates Ultra low in Cooling when thermostat is off.
2)
SEG18
3)
SEG20
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1)
4)
SEG21
DB68-11271A-02_IM_CAC Universal AHU Indoor_AA_EN_.indd 54 2022-09-15 오전 9:53:34