1. Specification
44
Wind-Free 4Way Cassette
Model Name
Indoor Unit AC120NN4DKH/EU AC140NN4DKH/EU AC140NN4DKH/EU
Outdoor Unit AC120MXADNH/EU AC140MXADKH/EU AC140MXADNH/EU
Outdoor
Unit
Power Supply Ø, #, V, Hz 3, 4, 380-415, 50 1, 2, 220-240, 50 3, 4, 380-415, 50
Heat
Exchanger
Type - Fin & Tube Fin & Tube Fin & Tube
Material
Fin - Al Al Al
Tube - Cu Cu Cu
Fin Treatment - Green Hydrophile Green Hydrophile Green Hydrophile
Compressor
Model Name UG5TK1450FJX UG5TK1450FJX UG5TK1450FJX
Output kW 4.19 4.19 4.19
Oil
Type - PVE PVE PVE
Initial charge cc 1700 1700 1700
Fan
Type - Propeller Propeller Propeller
Discharge direction - Front Front Front
Quantity EA 1 2 2
Air Flow Rate
CMM 78 111 111
l/s 1300 1850 1850
Fan Motor
Type - BLDC Motor BLDC Motor BLDC Motor
Output W x n 125 x 1 125 x 2 125 x 2
Sound
Sound Pressure
Level
Cooling dB(A) 54 53 53
Heating dB(A) 56 54 54
Sound Power Level dB(A) 70 69 69
External
Dimension
Net Weight kg 77 87 87
Shipping Weight kg 82 97 97
Net Dimensions (WxHxD) mm 940 x 998 x 330 940 x 1210 x 330 940 x 1210 x 330
Shipping Dimensions (WxHxD) mm 995 x 1096 x 426 995 x 1388 x 426 995 x 1388 x 426
Casing Material Body - EGI Steel Plate EGI Steel Plate EGI Steel Plate
Operating
Temp. Range
Cooling ℃ -15 ~ 50 -15 ~ 50 -15 ~ 50
Heating ℃ -20 ~ 24 -20 ~ 24 -20 ~ 24
NOTE
• Specification may be subject to change without prior notice.
Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Sound power level is an absolute value that a sound source generates.
Sound power level is based on cooling operation.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
3) These products contain R410A(GWP=2,088) which is fluorinated greenhouse gas.
• In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.