45
2. Summary Table
Wind-Free 4Way Cassette
2. Summary Table
Performance Characteristics
Model Code
Net
Weight
(kg)
Capacity
Fan Speed
Airflow
(Cooling/Heating)
(CMM)
Sound Pressure Level
(dBA)
Sound Power Level
(dBA)
Cooling
(kW)
Heating
(kW)
AC052NN4DKH/EU 15
Max. 6.0 7.0 High 15.0 / 15.0 33 49
Std. 5.0 6.0 Mid 14.0 / 14.0 31 -
Min. 1.0 1.0 Low 13.0 / 13.0 29 -
AC071NN4DKH/EU 15
Max. 8.0 9.0 High 19.5 / 19.5 36 53
Std. 7.1 8.0 Mid 16.5 / 16.5 33 -
Min. 2.2 1.9 Low 14.5 / 14.5 29 -
AC090NN4DKH/EU 18
Max. 11.3 13.9 High 30.0 / 30.0 43 60
Std. 9.0 10.0 Mid 24.0 / 24.0 38 -
Min. 3.0 2.2 Low 18.0 / 18.0 33 -
AC100NN4DKH/EU 18
Max. 12.0 15.5 High 31.0 / 31.0 44 61
Std. 10.0 11.2 Mid 25.0 / 25.0 39 -
Min. 3.0 2.2 Low 19.0 / 19.0 33 -
AC120NN4DKH/EU 18
Max. 13.5 15.5 High 32.0 / 32.0 45 61
Std. 12.0 13.0 Mid 26.0 / 26.0 40 -
Min. 3.5 3.5 Low 22.0 / 22.0 35 -
AC140NN4DKH/EU 20
Max. 15.5 18.0 High 34.0 / 34.0 45 61
Std. 13.4 15.5 Mid 27.0 / 27.0 41 -
Min. 3.5 3.5 Low 23.0 / 23.0 37 -
NOTE
• Sound data is based on cooling operation.
Electric Characteristics
Model Outdoor Unit Input Current (Amperes) Power Supply
Indoor Unit Outdoor Unit
Rated Voltage range Outdoor Unit
Indoor Unit Total MCA(A) MFA(A)
Hz Volts Min. Max. Cooling Heating
AC052NN4DKH/EU AC052MXADKH/EU 50 220 to 240 198 264 20 20 1 21 21 25
AC071NN4DKH/EU AC071MXADKH/EU 50 220 to 240 198 264 20 20 1 21 21 25
AC090NN4DKH/EU AC090MXADKH/EU 50 220 to 240 198 264 24 24 1 25 25 30
AC100NN4DKH/EU AC100MXADKH/EU 50 220 to 240 198 264 24 24 1 25 25 30
AC100NN4DKH/EU AC100MXADNH/EU 50 380 to 415 342 456.5 16.1 16.1 1 17.1 17.1 17.1
AC120NN4DKH/EU AC120MXADKH/EU 50 220 to 240 198 264 24 24 1 25 25 30
AC120NN4DKH/EU AC120MXADNH/EU 50 380 to 415 342 456.5 16.1 16.1 1 1 7.1 1 7.1 1 7.1
AC140NN4DKH/EU AC140MXADKH/EU 50 220 to 240 198 264 32 32 1 33 33 40
AC140NN4DKH/EU AC140MXADNH/EU 50 380 to 415 342 456.5 16.1 16.1 1 1 7.1 17.1 17.1
NOTE
• MCA : Minimum circuit amperes
• MFA : Maximum fuse amperes
• Select wire size based on the value of MCA