EasyManua.ls Logo

Samsung AC MN KH/EU Series - Page 90

Samsung AC MN KH/EU Series
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6. Capacity Correction
90
Outdoor Units
AC052/060MXADKH/EU
Cooling
Pipe Length (m)
5 10 15 20 25 30
Level Difference (m)
30 - - - - - -
25 - - - - - -
20 - - - 92 90
15 - - 94 92 90
10 - 96 94 92 90
5 98 96 94 92 90
0 100 98 96 94 92 90
-5 97 95 93 91 89
-10 - 94 93 91 89
-15 - - 92 90 88
-20 - - - - 89 86
-25 - - - - - -
-30 - - - - -
Heating
Pipe Length (m)
5 10 15 20 25 30
Level Difference (m)
30 - - - - - -
25 - - - - - -
20 - - - - 94 92
15 - - - 95 94 92
10 - - 97 95 94 92
5 - 98 97 95 94 92
0 100 98 97 95 94 92
-5 - 98 97 95 94 92
-10 - - 97 95 94 92
-15 - - - 95 94 92
-20 - - - - 94 92
-25 - - - - - -
-30 - - - - - -

Related product manuals