EasyManua.ls Logo

Samsung AC MN KH/EU Series - Page 91

Samsung AC MN KH/EU Series
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
91
6. Capacity Correction
Outdoor Units
AC071/090/100/120MXAD*H/EU
Cooling
Pipe Length (m)
5 10 15 20 25 30 35 40 45 50
Level Difference (m)
30 - - - - - - 93 92 91 90
25 - - - - - 94 93 92 91 90
20 - - - - 96 94 93 92 91 90
15 - - - 97 96 94 93 92 91 90
10 - - 98 97 96 94 93 92 91 90
5 - 99 98 97 96 94 93 92 91 90
0 100 99 98 97 96 94 93 92 91 90
-5 - 98 97 96 95 94 93 92 91 89
-10 - - 97 96 95 94 92 91 90 88
-15 - - - 95 95 93 92 91 89 88
-20 - - - - 94 93 92 90 89 87
-25 - - - - - 92 91 90 88 86
-30 - - - - - - 91 89 88 85
Heating
Pipe Length (m)
5 10 15 20 25 30 35 40 45 50
Level Difference (m)
30 - - - - - - 95 94 93 92
25 - - - - - 96 95 94 93 92
20 - - - - 96 96 95 94 93 92
15 - - - 97 96 96 95 94 93 92
10 - - 98 97 96 96 95 94 93 92
5 - 99 98 97 96 96 95 94 93 92
0 100 99 98 97 96 96 95 94 93 92
-5 - 99 98 97 96 96 95 94 93 92
-10 - - 98 97 96 96 95 94 93 92
-15 - - - 97 96 96 95 94 93 92
-20 - - - - 96 96 95 94 93 92
-25 - - - - - 96 95 94 93 92
-30 - - - - - - 95 94 93 92

Related product manuals