23
English
Installation
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation
PAGE
Use of external
control
Setting the output
of external control
S-Plasma ion Buzzer control
RESERVED
Indication and
details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
2
0
Disuse
0
Thermo
on
0 Disuse 0 Use
1
On/Off
control
2
Off
control
1
Operation
on
1 Use 1 Disuse
3
Window
on/off
control
Option SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
Explanation
PAGE
Individual control of
a remote controller
Heating setting
compensation
RESERVED RESERVED RESERVED
Indication and
details
Indication
Details
Indication
Details
Indication
Details
3
0 or 1 Indoor 1
0
Disuse
2 Indoor 2
3 Indoor 3
4 Indoor 4
1
2˚C
2
5˚C
If you input a number other than 0~4 on the individual control of the indoor unit(SEG 20), the indoor is set as "Indoor 1".
Example) If you want to set as "Exterior temperature sensor : USE, External control : USE
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 - 1 0 -
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 0 - - - 0
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 1 0 - 0 0
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 0 - - - -
assign option codes except SEG 1, 7, 13, 19 which are page options.
* Level control : The centralized controller can limit the functions and inputs of connected products with this function
enabled.
[ Example: Operation mode limit (Cooling only/Heating only/No limitation), Heating temperature upper
limit, Cooling temperature lower limit ]
To enable 'Level control' when applying the DPM with the centralized controller, appoint the master
(Set 'Use of external control [SEG14] option to 4 or higher).