16
Installation Procedure
English
Installation Procedure
Step 5 Connecting the refrigerant pipe
Items
Maximum allowable length
Single installation DPM installation
Applicable outdoor unit models AC036MXADKH
AC048MXADKH
AC054MXADKH
AC036MXADKH
AC048MXADKH
AC054MXADKH
Total pipe length (L
1
+…+L
n+1
+a+b) - - 50 m 75 m
Main pipe (L
1
) 50 m 75 m 30 m 50 m
Max. distance among indoor units (D) - - 10 m 10 m
Max. length after branch - - 15 m 15 m
Max. height difference between
outdoor and indoor units (h
1
)
30 m 30 m 30 m 30 m
Max. height difference among
indoor units(h
2
)
- - 0.5 m 0.5 m
Max Pipe length difference among
indoor units after branch
[L
2
-L
3
or L
2
-L
4
or L
2
-L
5
or a-b or (a+L
2
)-
(b+L
4
) or (a+L
3
)-(b+L
5
)]
- - 5 m 5 m
"n" means the number of indoor unit connection of DPM.
indoor
indoor
indoor
outdoor
outdoor
outdoor
indoor
indoor
indoor
indoor
indoor
indoor
indoor
outdoor
L
1
L
1
L
2
L
2
D
D
D
D
h
2
h
2
L
3
L
3
L
4
L
4
L
5
L
1
a
b
D
L
1
L
2
L
3
h
1
h
2
h
1
h
1
h
1
n=1
n=2
n=3
n=4
Use a joint kit that is only for DPM.
Temper grade and minimum thickness of the refrigerant pipe
Outer diameter [mm] Minimum thickness [mm] Temper grade
ø6.35 0.7
C1220T-O
ø9.52 0.7
ø12.70 0.8
ø15.88 1.0
ø15.88 0.8
C1220T-1/2H OR C1220T-Hø19.05 0.9
ø22.23 0.9