EasyManua.ls Logo

Samsung AC RN DKG Series - Spacing Requirements

Samsung AC RN DKG Series
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Installation Procedure
Installation Procedure
English
Spacing requirements
2500 mm or more
Obstruction
1500 mm or
more
20 mm
B
A
Model
AC026RN1DKG
AC035RN1DKG
AC052RN4DKG
AC071RN4DKG
AC100RN4DKG
AC120RN4DKG
AC140RN4DKG
A 170 mm 251 mm 355 mm
B 15 mm 17 mm 17 mm
(Unit: mm)
1 way Cassette
C: 1500 mm or more
C
C
C
C
4 way Cassette
C: 1500 mm or more
C
C
C
C
CAUTION
ŷ Comply with the length and height limits described in
the figure above.
ŷ For the product that uses the R-32 refrigerant, Install
the indoor unit on the wall 1.8 m or higher from the
floor.
ŷ The indoor unit must be installed according to the
specified distances in order to permit accessibility
from each side, to guarantee correct operation,
maintenance, and repair of the unit. The components
of the indoor unit must be reachable and removable
under safe conditions for people and the unit.
ŷ Do not hold the discharge while carrying the indoor
unit to avoid the possibility of breakage.
ŷ You must hold the hanger plate on the corner and
carry the indoor unit.

Related product manuals