24
Indoor Unit Installation
Installation
• The external output of SEG15 is generated by MIM-B14 connection. (Refer to the manual of MIM-B14.)
After disassembling the cover
panel, you can connect the
wires from the indoor unit's
display to the wired remote
control and MIM-B14.
Be sure to connect the wired
remote control for installation
after cutting the COM2 wire.
4 PIN : Error check
(MIM-B14)
2 PIN : External ON/OFF
Control(MIM-B14)
COM2(F3, F4) :
F3/F4
If you input a number other than 0~4 on the individual control of the indoor unit(SEG 20), the indoor is set as "Indoor 1".
Example) If you want to set as "Exterior temperature sensor : USE, External control : USE
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 - 1 0 -
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 0 - - - 0
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 1 0 - 0 0
SEG19 SEG20 SEG21 SEG22 SEG23 SEG24
3 0 - - - -
Assign option codes except SEG 1, 7, 13, 19 which are page options.
* Level control : The centralized controller can limit the functions and inputs of connected products with this function enabled.
[Example: Operation mode limit (Cooling only/Heating only/No limitation), Heating temperature upper limit,
Cooling temperature lower limit]
To enable 'Level control' when applying the DPM with the centralized controller, appoint the master
(Set Use of external control [SEG14] option to 4 or higher).