Installation Procedure
Main power terminal block specifications
1-phase terminal block specifications
(Unit: mm)
AC090/100/120/140/160/TXAPKG
1(L) 2(N)
F1 F2
L N
16.3 12 11.4
10.1
3-phase terminal block specifications
(Unit: mm)
AC100/120/140/160/TXAPNG
1(L) 2(N) L1(R) L2(S) L3(T) N
9.8 14.2 11.4
F1 F2
10.1
Main power cable specifications
The power cable is not supplied with air conditioner.
Select the power supply cable in accordance with relevant local and national regulations.
Wire size must comply with the applicable local and national code.
Specifications for local wiring power cord and branch wiring are in compliance with local cord.
Single phase
Model Outdoor unit Input current (A) Power supply
Indoor unit Outdoor unit Hz
Voltage range (V) Outdoor unit
Indoor unit Total MCA (A) MFA (A)
Rated Min. Max. Cooling Heating
AC090TNHDKG
AC090TXAPKG
50 220 to 240 198 264
24 24
2.3 26.3 26.3 30.0
AC100TN4DKG
AC100TXAPKG
1.5 25.5 25.5 30.0
AC100TN4PKG
1.5 25.5 25.5 30.0
AC100TNHDKG
2.7 26.7 26.7 30.0
AC120TN4DKG
AC120TXAPKG
32 32
1.5 33.5 33.5 40.0
AC120TN4PKG
1.5 33.5 33.5 40.0
AC120TNHDKG
2.9 34.9 34.9 40.0
AC140TN4DKG
AC140TXAPKG
1.5 33.5 33.5 40.0
AC140TN4PKG
1.5 33.5 33.5 40.0
AC140TNHDKG
3.5 35.5 35.5 40.0
AC160TNHFKG
AC160TXAPKG 3.1 35.1 35.1 40.0
CAC_R32_AU_Outdoor IM_EN_DB68-08522A-00_.indd 13 2019-08-19 오전 10:10:59