19English
Installation Procedure
7 After tube contraction work is completed, wrap it with
the insulation tape to finish.
Three or more layers of insulation are required.
IInsulation tape
Insulation tape
Method 1 Method 2
CAUTION
Make sure that the connection parts are not exposed
to outside.
Be sure to use insulation tape and a contraction tube
made of approved reinforced insulating materials that
have the same level of withstand voltage with the
power cable. (Comply with the local regulations on
extensions.)
WARNING
In case of extending the electric wire, please DO NOT
use a round-shaped Pressing socket.
Incomplete wire connections can cause electric
shock or a fire.
Step 5 Connecting the refrigerant pipe
Items
Maximum allowable length
Single Installation
Applicable outdoor
unit models
AC090TXAPKG
AC100TXAP*G
AC120TXAP*G
AC140TXAP*G
AC160TXAP*G
Main pipe (L1) 50 m 85 m
Max. height
difference between
outdoor and
indoor units (h1)
30 m 30 m
"n" means the number of indoor unit connection of
DPM.
indoor
outdoor
L
1
h
1
n=1
Temper grade and minimum thickness of the
refrigerant pipe
Outer diameter
[mm]
Minimum
thickness [mm]
Temper grade
ø6.35 0.7
C1220T-O
ø9.52 0.7
ø12.70 0.8
ø15.88 1.0
ø15.88 0.8
C1220T-1/2H
OR C1220T-H
ø19.05 0.9
ø22.23 0.9
CAC_R32_AU_Outdoor IM_EN_DB68-08522A-00_.indd 19 2019-08-19 오전 10:11:01