17English
Installation Procedure
• Connect the rated cables only.
• Connect using a driver which is able to apply the
rated torque to the screws.
• If the terminal is loose, fire may occur caused by arc.
If the terminal is connected too firmly, the terminal
may be damaged.
Tightening torque (N⋅m)
M4 0.8 to 1.2
M5 2.0 to 3.0
• 1 N⋅m = 10 kgf⋅cm
CAUTION
• When connecting cables, you can connect the cables
to the electrical part or connect them through the
holes below depending on the spot.
• Connect the communication cable between the
indoor and outdoor units through a conduit to protect
against external forces, and feed the conduit through
the wall together with refrigerant piping.
• Remove all burrs at the edge of the knock-out hole
and secure the cable to the outdoor knock-out using
lining and bushing with an electrical insulation such
as rubber and so on.
• Must keep the cable in a protection tube.
• Keep distances of 50mm or more between power
cable and communication cable.
• When the cables are connected through the hole,
remove the Plate bottom.
Outdoor-to-indoor power and communication
cables specifications
Indoor power supply
Power supply Max/Min (V) Indoor power cable
1ø, 220-240V,
50 Hz
±10% 1.5 mm²
↑
, 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
• Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
• When installing the indoor unit in a computer room
or net work room, use the double shielded (tape
aluminium / polyester braid + copper ) cable of
FROHH2R type.
Step 4 Optional: Extending the power
cable
1 Prepare the following tools.
Tools Spec Shape
Crimping pliers MH-14
Connection sleeve
(mm)
20xØ6.5
(HxOD)
Insulation tape
Width 19
mm
Contraction tube
(mm)
70xØ8.0
(LxOD)
CAC_R32_AU_Outdoor IM_EN_DB68-08522A-00_.indd 17 2019-08-19 오전 10:11:00