Adding refrigerant (R-410A)
The outdoor unit is loaded with sucient refrigerant for the standard piping. Thus, refrigerant must be added if the piping is
lengthened. This operation can only be performed by a qualied refrigeration specialist. For quantity of adding refrigerant, refer
to page 19.
1. Check that the stop valve is closed entirely.
2. Charge the refrigerant through the service port of liquid stop valve.
t %POPUDIBSHFUIFSFGSJHFSBOUUISPVHIUIFHBTTJEFTFSWJDFQPSU
NOTE
3. If you cannot charge the refrigerant according to the upper steps, following these :
1) Open both liquid stop valve and gas stop valve.
2) Operate the air conditioner by pressing the K2 key on the outdoor unit PCB.
3) About 30 minutes later, charge the refrigerant through the service port of gas stop valve.
t *GOFDFTTBSZSFGFSUPUIFQSFTTVSFUBCMFDMBTTJöFECZPVUEPPSUFNQFSBUVSF
NOTE
1
Ref.
Gas side stop valve(service port)
Outdoor unit
Indoor unit
Balance Vacuum pump
Liquid side stop valve(service port)
How to Calculate the Quantity of Adding Refrigerant
X
The outdoor unit is loaded with sucient R-410 A refrigerant for 24.6 ft(7.5 m) of piping.
If you have used more than “24.6 ft(7.5 m)”, add "A" of refrigerant for extra meter.
The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit
situation before adding refrigerant.
This operation can only be performed by a qualied refrigeration specialist.
Outdoor Unit Pipe length [ft(m)]
"A" Unit amount of refrigerant [oz/ft(g/m)]
AC018MXSCCC
24.6 ~ 98.4 (7.5 ~ 30) 0.161 (15)
AC024MXSCCC
24.6 ~ 164.0 (7.5 ~ 50) 0.108 (10)
02 INSTALLATION
English-19