14
Installation Procedure
English
Installation Procedure
NOTE
RLA is based on AHRI 210/240 cooling standard
condition [Indoor temp. : 26.7 °C / 80 °F(DB) / 19.46°C /
67°F(WB), Outdoor temp. : 35 °C / 95 °F(DB)]
Voltage tolerance is ± 10%.
Maxium allowable voltage between phases is 2%.
Symbols
RLA: Rated Load Ampere (A)
MOC: Maximum Operating Current (A)
MCA: Minumum Circuit Ampere (A)
MOP: Maximum Overcurrent Protective Device (A)
Voltage range
Units are suitable for use on electrical systems
where voltage supplied to unit terminal is not
below or above listed range limits.
Maximum allowable voltage variation between phases
is 2%.
Wire size & type must comply with the applicable local
and national code.
Wire size: Based on the value of MCA.
Wire type:
1-phase: 60245 IEC57(IEC) or H05RN-F(CENELEC)
grade or more
Silence mode controller wiring diagram with
External controller
AC018BXADCH
2Pin
(RED)
4Pin
(RED)
Non-voltage contact
External controller
AC024/030/036/042/048BXADCH
2Pin (RED)
4Pin(RED)
Non-voltage
contact
External controller
DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 14DB68-11274A-00_IM_CAC Universal Outdoor_AA_EN.indd 14 2021-09-14 오전 9:21:582021-09-14 오전 9:21:58