26
Installation Procedure
English
Installation Procedure
Step 12 Insulating the refrigerant
pipes
1 Once you have checked that there are no leaks in the
system, you can insulate the piping and hose.
No gap
NBR
NOTE
When insulate the pipe, be sure to overlap the
insulation.
The insulation has to be produced in full compliance
of European regulation reg. EEC / EU 2037/ 2000
that requires the use of sheaths insulation form
without using CFC and HCFC gases for health and the
environment.
CAUTION
When insulating the pipe, use non-slit insulator.
2 Select the insulation of the refrigerant pipe.
Insulate the gas side and liquid side pipe referring
to the thickness according to the pipe size.
Less than Indoor temperature of 86℉(30℃) and
humidity of 85% is the standard condition. If
installing in a high humidity condition, use one
grade thicker insulator by referring to the table
below. If installing in an unfavourable conditions,
use thicker one.
Insulator’s heat-resistance temperature should be
more than 248℉(120℃).
Pipe
Outer diameter
Insulation Type
(Cooling, Heating)
Remarks
General
[86°F(30°C),
85%]
High humidity
[86°F(30°C),
over 85%]
EPDM,NBR
mm inch mm inch mm inch
Liquid
pipe
6.35~9.52 1/4~3/8 9 3/8 9 3/8
Heating
resisting
temperature
over
248°F(120°C)
12.7~50.80 1/2~2 13 1/2 13 1/2
Gas
pipe
6.35 1/4 13 1/2 19 3/4
9.52~25.4 3/8~1 19 3/4 25 1
28.58~44.45
1 1/8~1
3/4
19 3/4 32 1 1/4
50.8 2 25 1 38 1 1/2
When installing insulation in places and
conditions below, use the same insulation that is
used for high humidity conditions.
<Geological condition>
High humidity places such as shoreline, hot spring,
near lake or river, and ridge (when the part of the
building is covered by earth and sand.)
<Geological condition>
Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
The ceiling frequently exposed to moisture and
cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory
and studio or near an exit that opens and closes
frequently.
The place where the pipe is installed is highly
humid due to the lack of ventilation system.
Step 13 Checking the earthing
If the power distribution circuit does not have a earthing
or the earthing does not comply with specifications, an
earthing electrode must be installed. The corresponding
accessories are not supplied with the air conditioner.
1 Select an earthing electrode that complies with the
specifications given in the illustration.