EasyManua.ls Logo

Samsung AC035MXADKH/EU - Page 16

Samsung AC035MXADKH/EU
117 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wind-Free 4Way Cassette (600x600)
1. Specification
16
Model Name
Indoor Unit AC060NNNDKH/EU AC071NNNDKH/EU
Outdoor Unit AC060MXADKH/EU AC071MXADKH/EU
Outdoor
Unit
Power Supply Ø, #, V, Hz 1, 2, 220-240, 50 1, 2, 220-240, 50
Heat
Exchanger
Type - FMC FMC
Material
Fin - Al Al
Tube - Al Al
Fin Treatment - Hybrid Coating Hybrid Coating
Compressor
Model Name UG9TK3150FE4 UG4T200FUAE4
Output kW 1.42 1.79
Oil
Type - POE POE
Initial charge cc 500 650
Fan
Type - Propeller Propeller
Discharge direction - Front Front
Quantity EA 1 1
Air Flow Rate
CMM 40 51
l/s 667 850
Fan Motor
Type - BLDC Motor BLDC Motor
Output W x n 125 x 1 125 x 1
Sound
Sound Pressure
Level
Cooling dB(A) 49 49
Heating dB(A) 49 51
Sound Power Level dB(A) 62 65
External
Dimension
Net Weight kg 43.8 53
Shipping Weight kg 4 7. 5 57. 2
Net Dimensions (WxHxD) mm 880 x 638 x 310 880 x 798 x 310
Shipping Dimensions (WxHxD) mm 1023 x 730 x 413 1023 x 911 x 413
Casing Material Body - EGI Steel Plate EGI Steel Plate
Operating
Temp. Range
Cooling -15 ~ 50 -15 ~ 50
Heating -20 ~ 24 -20 ~ 24
NOTE
Specification may be subject to change without prior notice.
Specification comply with EN14511.
1) Capacities are based on (Equivalent refrigerant piping 5m, Level differences 0m);
- Cooling : Indoor temperature 27°C DB, 19°C WB / Outdoor temperature 35°C DB, 24°C WB
- Heating : Indoor temperature 20°C DB, 15°C WB / Outdoor temperature 7°C DB, 6°C WB
2) Sound power level is an absolute value that a sound source generates.
Sound power level is based on cooling operation.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are obtained in an anechoic room.
Sound values of multi combination are theoretical values based on sound results of individual installed units.
3) These products contain R410A(GWP=2,088) which is fluorinated greenhouse gas.
In case you want to know more information regarding capacity and correction, please refer to capacity table
TDB on pvi.samsung.com site.

Other manuals for Samsung AC035MXADKH/EU

Related product manuals