91
6. Capacity Correction
Outdoor Units
AC071/090/100/120MXAD*H/EU
Cooling
Pipe Length (m)
5 10 15 20 25 30 35 40 45 50
Level Difference (m)
30 - - - - - - 93 92 91 90
25 - - - - - 94 93 92 91 90
20 - - - - 96 94 93 92 91 90
15 - - - 97 96 94 93 92 91 90
10 - - 98 97 96 94 93 92 91 90
5 - 99 98 97 96 94 93 92 91 90
0 100 99 98 97 96 94 93 92 91 90
-5 - 98 97 96 95 94 93 92 91 89
-10 - - 97 96 95 94 92 91 90 88
-15 - - - 95 95 93 92 91 89 88
-20 - - - - 94 93 92 90 89 87
-25 - - - - - 92 91 90 88 86
-30 - - - - - - 91 89 88 85
Heating
Pipe Length (m)
5 10 15 20 25 30 35 40 45 50
Level Difference (m)
30 - - - - - - 95 94 93 92
25 - - - - - 96 95 94 93 92
20 - - - - 96 96 95 94 93 92
15 - - - 97 96 96 95 94 93 92
10 - - 98 97 96 96 95 94 93 92
5 - 99 98 97 96 96 95 94 93 92
0 100 99 98 97 96 96 95 94 93 92
-5 - 99 98 97 96 96 95 94 93 92
-10 - - 98 97 96 96 95 94 93 92
-15 - - - 97 96 96 95 94 93 92
-20 - - - - 96 96 95 94 93 92
-25 - - - - - 96 95 94 93 92
-30 - - - - - - 95 94 93 92