13
Installation Procedure
English
• Ifitisnecessarytoincreasetheheightofthedrain
pipe,installthedrainpipestraightwithin300mm
fromthedrainhoseport.Ifitisraisedhigherthan550
mm,theremaybewaterleaks.
Band joint
300 mm or
less
550 mm or
less
20 mm or more
1/100 or more
Drain hose
Ceiling
• Donotgivethehoseanupwardgradientbeyondthe
connectionport.Thiswillcausewatertoflowbackwards
whentheunitisstopped,resultinginwaterleaks.
Under gradient
Ceiling
• Donotapplyforcetothepipingontheunitsidewhen
connectingthedrainhose.Thehoseshouldnotbe
allowedtohangloosefromitsconnectiontotheunit.
Fastenthehosetoawall,frameorothersupportas
closetotheunitaspossible.
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
• Installhorizontally.
Indoor unit
Be horizontal
Flexible hose
• Max.allowableaxisgap.
Indoor unit
Max. 20 mm
• Max.allowablebendingangle.
Max. 30˚
Indoor unit
NOTE
• Ifaconcentrateddrainpipeisinstalled,refertothe
figurebelow.
CAC R-32_Mini 4way_IM_DB68-08129A-00_EN_20181211.indd 13 2018/12/11 11:30:21