EasyManua.ls Logo

Samsung AC071MN4PKH - Page 17

Samsung AC071MN4PKH
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
Installation Procedure
English
Wiring terminals) 3 phase
1(L) 2(N) L1(R) L2(S) L3(T) N
F1 F2
F1 F2
L
N
Indoor power
Main power cable
Communication
cable
Indoor unit
Outdoor unit
NOTE
ŷ Insert the power and the communication cables to
the cable insert hole, then arrange and connect the
cables, as shown in the figure:
Cable insert
hole
Power cable Communication
cable
Indoor power supply
Power supply Max/Min(V) Indoor power cable
220 to 240V, 50 Hz
±10%
0.75 to 1.5 mm², 3 wires
Communication cable
0.75 to 1.5 mm², 2 wires
AC power: M4 screw
Communication: M3.5 screw
11
13
7.5
9.0
18
13.8
7LJKWHQLQJWRUTXHNJIŷFP
M3.5 8.0 to 12.0
M4 12.0 to 18.0
ŷ 1yP NJIyFP
ŷ Power supply cords of parts of appliances for
outdoor use shall not be lighter than polychloroprene
sheathed flexible cord. (Code designation IEC:60245
IEC 57 / CENELEC: H05RN-F or IEC:60245 IEC 66 /
CENELEC: H07RN-F)
ŷ Since it has the external power supply, refer to the
outdoor unit installation manual for MAIN POWER.
CAUTION
ŷ When installing the indoor unit in a computer
room or network room, use the double shielded
communication cable (tape aluminum / polyester
braid + copper) of FROHH2R type.

Other manuals for Samsung AC071MN4PKH