7
Installation Procedure
English
Spacing requirements
A
A : 1500 mm or more
A
A
A
'C'
Indoor unit
2500 mm or more
Obstruction
20 mm
1500 mm or
more
10 mm
(Unit: mm)
Model AC071MN4PKH AC090MN4PKH AC100MN4PKH AC120MN4PKH AC140MN4PKH
C 261 345 345 345 345
Model AC071MN4PKH AC090MN4PKH AC100MN4PKH AC120MN4PKH AC140MN4PKH
Chassis Small Large Large+
Net dimension (W
× D × H)
mm 947 X 947 X 281 947 X 947 X 365 947 X 947 X 365 947 X 947 X 365 947 X 947 X 365
Net weight kg 20.2 23.5 23.5 23.5 25.5
Liquid pipe connection 6.35 9.52 9.52 9.52 9.52
Gas pipe connection 15.88 15.88 15.88 15.88 15.88
Drain hose
connection
mm Outer diameter: Ø32, Inner diameter: Ø26.5
ŷ The circular panel is by default available in exposed
installation.
ŷ Make inspection holes on the ceiling for easier
installation and maintenance, as shown in the
following table. (The size of an inspection hole must
be at least 450 mm x 450 mm.)
ŷ A suspended ceiling structure can substitute for the
inspection holes.
Category
Inspection hole
Recessed installation
Exposed
installation
Integrated suspended
Square panel
1 ea
-
Circular panel
2 ea
ŷ
For the recessed installation of the circular panel
Refrigerant
pipe
Connection part of the
drain hose
Indoor unit
display
Inspection hole
1050
883
ø1010 to 1020
Ceiling opening diameter
ø1010 to 1020
Inspection hole
NOTE
The clearance between the panel and the inspection hole
is 15 to 20 mm on a side.