4-40 Samsung Electronics
1. E465 : Compressor over load error
•Ifacompressorworksimproperly,changethecompressorandcheckifitworksproperly.
If a compressor is normal, check the assembly between Heatsink-Inverter PBA. If it is fine, change Inverter PBA.
2. E468 : Current sensor error
•
Check EEPROM data.
•
Check PCB operates properly.
3. E471 : Oudoor EEPROM error
Upload EEPROM on Outdoor unit Main PBA.
4. E474 : IPM(IGBT Module) or PFCM Temperature sensor Error
E500 : IPM is over heated
Check IPM is well assembled to heatsink
Check whether inlet port is clogged.
Change IPM if it is defective one
5. E554 : Gas leak error
Check refrigerant charge
Check Indoor EVA sensor
Check Service valve is open.
Check the pipes and wires correctly connected.
6. E556 : Capacity miss match between indoor and outdoor
•
Check the model name of indoor and outdoor unit and set option code on indoor unit again.
7. Outdoor overload protection control (at the stop of the compressor.) : E404
•
Check whether the fan and the motor operate normally.
•
Check the operation of EEV.
•
Check the temperature sensor of the indoor unit heat exchanger.
•
Check the indoor unit inlet blocking.