EasyManua.ls Logo

Samsung AC200KNHPKH - Float Switch(Open)

Samsung AC200KNHPKH
96 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Samsung Electronics 4-9
Wire remote controller display
E153
Symptom
2nd Detection of the float switch
Failure
Float switch open
4-3-3 Float switch(Open)
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Remove the floating sensor
connector connected to the indoor unit
PCB and the resistance measured between the
two terminals. Is the resistance ∞?
(open circuit)
Is the water level in the drain pan high?
Does drain pump operate
when compressor operates?
Same error occurs again
No
Drain pump PCB
Is the terminal voltage around
DC12V?
Is the water level in
drain pan decreasing?
Reset the indoor unit power and
check the operation of the drain pump.
(it vibrates when operating)
Normal operation
Replace the indoor unit PCB
Reassemble the floating sensor
connector and reset the outdoor unit
power. (Indoor unit power reset is
required)
Normal operation
Replace the floating sensor
when it fails and reset the
indoor unit power
Replace the drain pump
Replace the drain pump Replace the indoor unit PCB
Error occurs
• Floatsensorerrorisclearedonly
when the indoor power is reset

Table of Contents

Other manuals for Samsung AC200KNHPKH

Related product manuals